Gas leak detectors, analyzers, alarm devices and calibration gas
SKU# (901)

SPECTREX  40/40L-111AC

$2,477.14     Availability: 3 Weeks
 Info/Quote Request
 Shipping Rates
 Volume discount



SPECTREX 40/40L_-111AC (1)
  • Overview
  • Benefits
  • Specs
  • Related
  • Literature

SPECTREX SharpEye 40/40L Flame Detector with UV (ultraviolet) and IR(infrared) (2.5-3.0 um) sensor for hydrocarbon-based fuel and gas fires, hydroxyl and hydrogen fires, metal and inorganic fires. 3 Relays (Alarm, Fault and Auxiliary), 0-20mA stepped, compatible with RS-485 Modbus. Built-in-test (BIT) optional. Ex approved for Zone 1, ATEX, IECEx, FM and CSA Class I Div 1. 5 year warranty and is SIL2 (TUV) approved to IEC 61508

Part# with Options:        40/40L-111AC
Price with Options:        2,477.14

Options:    

Self Test
(1) Built-in self test for Spectrex SharpEye (L)
Wiring Option
(2) Output configuration for Spectrex
NO= Normally Open contact / NC= Normally Closed contact / RS-485 available on all options
Temperature
(3) Spectrex
Entry
(4) Conduit Entry for Spectrex
Enclosure
(5) Stainless Steel Enclosure for Spectrex SharpEye
Agency Approval
(6) Spectrex SharpEye
Mount
(7) Mount for Spectrex (40/40-001 & 777670)
PM Pole mount requires TM tilt mount for installation with 40/40 flame detectors
Cover
(8) Weather Cover for Spectrex (777263 or 777163)
EOL Resistor
(9) EOL Resistor for Spectrex SharpEye 40/40
Cone Viewer
(10) Cone Viewer for Spectrex SharpEye 40/40 (777166)

  Availability 3 Weeks  ]

The UV/IR flame detector senses radiant energy in the short wave section of both the ultraviolet and infrared portions of the electromagnetic spectrum. The signals from both sensors are analyzed for frequency, intensity and duration. Simultaneous detection of radiant energy in both the UV and IR sensors triggers an alarm signal.

The UV sensor incorporates a special logic circuit that helps prevent false alarms caused by solar radiation.

Features
  • UV/IR Dual-Sensor
  • High-Speed Response - 150 msec Response to Saturated
    Signal
  • Solar blind
  • Automatic and Manual Built-In-Test (BIT) - to assure continued reliable operation
  • Heated window - for operation in harsh weather conditions (snow, ice, condensation)
  • Multiple output options for maximum flexibility and compatibility
    • Relays (3) for Alarm, Fault and Auxiliary
    • 0-20mA (stepped)
    • HART Protocol for maintenance and asset management
    • RS-485, Modbus Compatible
  • High Reliability - MTBF - minimum 150,000 hours
  • Approved to Safety Integrity Level 2 (SIL2 – TUV)
  • 5-Year Warranty
  • User Programmable via HART or RS-485
  • Ex approved for Zone 1 hazardous area location
    • ATEX
    • IECEx
    • FM
    • CSA
  • 3rd party Performance Tested
    • EN54-10 (LPCB)
    • FM3260 (FM)
Applications
Offshore Oil & Gas installations Printing Industry
Onshore Oil & Gas installations and pipelines Warehouses
Chemical plants Automotive Industry
Petrochemicals plants Explosives & Munitions
Storage Tank farms Waste Disposal facilities
Aircraft hangars Aerospace Industry
Pharmaceutical Industry Paint, Polymer and Glue
processes

GENERAL SPECIFICATIONS
Spectral Response 40/40L–LB: UV: 0.185 - 0.260 μm; IR: 2.5-3.0 μm
40/40L4–L4B: UV: 0.185 - 0.260 μm; IR: 4.4-4.6 μm
Detection Range
(at highest Sensitivity Setting for 1ft2 (0.1m2) pan fire)
Fuel ft / m
n-Heptane 50 / 15
Gasoline 50 / 15
Diesel Fuel 37 / 11
JP5 37 / 11
Kerosene 37 / 11
Ethanol 95% 25 / 7.5
Methanol 25 / 7.5
IPA (Isopropyl Alcohol 25 / 7.5
Hydrogen** 16 / 5
Methane* 16 / 5
LPG * 16 / 5
Polypropylene Pellets 13 / 4
Office Paper 16 / 5
* 20" (0.5m) high, 8" (0.2m) width plume fire
** 40/40L/LB only
Response Time Typically 5 seconds. High speed 150 msec response to saturated signal
Adjustable Time Delay Up to 30 seconds
Sensitivity Ranges 1 ft2 (0.1m2) n-heptane pan fire from 50 ft (15m)
Field of View Horizontal 100º; Vertical 95º
Built-in-Test (BIT) Automatic (and Manual)
Temperature Range Operating: -67ºF to +167ºF (-55ºC to +75ºC)
Option: -67ºF to +185ºF (-55ºC to +85ºC)
Storage: -67ºF to +185ºF (-55ºC to +85ºC)
Humidity Up to 95% non-condensing (withstands up to 100% RH for short periods)
Heated Optics To eliminate condensation and icing on the window
ELECTRICAL SPECIFICATIONS
Operating Voltage 24 VDC nominal (18-32 VDC)
Power Consumption Standby: Max. 100mA (150mA with heated window)
Alarm: Max. 150mA (200mA with heated window)
Cable Entries 2 x 3/4" - 14NPT conduits or 2 x M25 x 1.5 mm ISO
Wiring 12 - 22AWG (2.5mm 2 - 0.3mm 2)
Electrical Input Protection According to MIL-STD-1275B
Electromagnetic Compatibility EMI/RFI protected to EN50130-4
Electrical Interface The detector includes twelve (12) terminals with five (5) wiring options (factory set)
OUTPUTS
Relays Alarm, Fault and Auxiliary
SPST volt-free contacts rated 5A at 30 VDC or 250 VAC.
0-20mA (stepped) Sink (source option) configuration
Fault: 0 +1mA
BIT Fault: 2mA ± 10%
Normal: 4mA ± 10%
IR: 8mA ± 5%
UV: 12mA ± 5%
Warning: 16mA ± 5%
Alarm: 20mA ± 5%
Resistance Loop: 100-600 Ω
HART Protocol HART communication on the 0-20mA analog current (FSK) - used for maintenance, configuration changes and asset management
RS-485 RS-485 Modbus compatible communication link that can be used in computer controlled
installations
MECHANICAL SPECIFICATIONS
Materials
Enclosure options
- Stainless Steel 316L with electro polish finish
- Heavy duty copper free aluminum (less than 1%), red epoxy enamel finish
Mounting Stainless Steel 316L with electro polish finish
Dimensions Detector 3.5" x 4.5" x 6.1" (90 x 114 x 156 mm)
Weight Detector (St.St.) 5.5 lb (2.5 kg)
Detector, aluminum 2.5 lb (1.2 kg)
Tilt mount 2.2 lb (1.0 kg)
Environmental Standards Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp
Water and Dust IP66 and IP67 per EN60529, NEMA 250 6P
APPROVALS
Hazardous Area
ATEX and IECEx Ex II 2 GD,  
  Ex de IIB+H2 T5 o (-5+55 ºCºC 7 x de IIB+H2 T4 (-55ºC to + 85ºC)
  Ex tD A21 IP66/X7 T 95ºC Ex tD A21 IP66/X7 T 105ºC
FM / CSA Class I Div. 1, Groups B, C & D  
  Class II/III Div. 1, Groups E, F & G  
Performance EN54-10 (LPCB)
FM-3260 (FM)
Reliability IEC61508 - SIL2 (TUV)
ACCESSORIES
Fire Simulator20/20-310
Weather Protector777163
Laser Pointer
(Detector area coverage)
777166
Tilt Mount40/40-003
Air Shield777161
Export Info
Made inUSA
Harmonized Tariff Code (HTC)90318099

  • ACCESSORIES > SPECTREX FLAME DETECTORS
    40/40-001 Tilt mount for SPECTREX SharpEye 40/40 series flame detectors, stainless steel. ..

  • ACCESSORIES > SPECTREX FLAME DETECTORS
    777163 Weather cover (Stainless Steel) for SPECTREX SharpEye 40/40 series flame detectors. ..

  • ACCESSORIES > SPECTREX FLAME DETECTORS
    777650 Air Shield for SPECTREX SharpEye flame detectors ..

  • ACCESSORIES > SPECTREX FLAME DETECTORS
    777670 Duct mount for SPECTREX SharpEye 40/40 series flame detectors, stainless steel. ..

  • ACCESSORIES > SPECTREX FLAME DETECTORS
    789260-2 Pole mount (U-bolt) - 2" for SPECTREX SharpEye flame detectors (does not include required 40/40-001 tilt mount) ..

  • ACCESSORIES > SPECTREX FLAME DETECTORS
    794079-5 USB RS485 Harness Kit with RS485/232 converter, used with Spectrex Host software, enables the user to connect to any available PC or laptop to re-configure settings or perform diagnostics on all 40/40 and 20/20 series flame detectors. Includes Host Softw ..

  • ACCESSORIES > SPECTREX FLAME DETECTORS
    888810 Emerson HART Hand-Held Diagnostics Unit c/w converter and cable harness (1m), software and manual in case. For SPECTREX SharpEye flame detectors ..

  • ACCESSORIES > SPECTREX FLAME SIMULATORS
    FS-1200 SPECTREX FS-1200 Long range flame simulator for all Spectrex UV and UV/IR Flame Detectors. Approved for Zone 1 and Zone 2 hazardous areas. Up to 26ft testing distance. Includes rechargeable Lithium-ion battery, charger, built-in beam collimator, tool kit ..


B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer, Check and Money Order

Checkout with Paypal

> FLAME DETECTORS > ULTRAVIOLET/INFRARED :    6 Items found.
100-0003-01
(4719)

ESP SAFETY  100-0003-01

ESP Safety IPES-IR/UV Infrared/Ultraviolet Flame Detector for detection of oil and petrochemical product fires. Rapid flame recognition and alar signaling. 4.2 to 4.6 microns (infrared) and 180 to 250 nanometers (ultraviolet) ranges. 90 degree field of view. RS-485, 4-20mA and relay outputs. Color status LED. Explosion-proof Housing. Designed for Class I, Division 1, Group B, C & D. SIL3 Rated. Includes protective visor, stainless steel mounting bracket and hardware.

Configure

$1,656.00 
20/20ML-11SF
(2935)

SPECTREX  20/20ML-11SF

SPECTREX Sharp Eye 20/20ML Mini UV/IR Flame Detector for detection of gasoline, n-heptane, diesel, jp5, kerosene, alcohol, ,IPA, methanol, methane, propane, hydrogen, silane, polypropilene and paper fires. Low cost, stainless steel enclosure, compact and lightweight. Highly resistant to harsh environments, immune to false alarms and designed for OUTDOOR or INDOOR applications. 2 Relays (Alarm and Fault), 0-20mA (sink or source) and compatible with RS-485 Modbus. Stainless steel housing. Available Approvals: FM only.

Configure

$1,848.21 
40/40L4_-111AC
(904)

SPECTREX  40/40L4-111AC

SPECTREX SharpEye 40/40L4 Flame Detector with UV and IR (4.5 um) sensor for hydrocarbon-based fuel and gas fires. Fast Response (200 msec) to flash fire 3 Relays (Alarm, Fault and Auxiliary), 0-20mA stepped, compatible with RS-485 Modbus. Built-in-test (BIT) optional. Ex approved for Zone 1, ATEX, IECEx, FM and CSA Class I Div 1. 5 year warranty and is SIL2 (TUV) approved to IEC 61508

Configure

$2,475.79 
FS20X-211-212
(2986)

HONEYWELL  FS20X-211-212

Honeywell Fire Sentry FS20X Multi-Spectrum (UV/Dual IR/VIS) Fire and Flame Detector for hydrocarbon and non-hydrocarbonfuel fires in all industrial enviromental conditions. 90° field of view. RS-485 MODBUS communication and 0-20 mA stepped analog output. Includes fire, fault and auxiliary relays. NEMA 4 & 4X enclosure. IP66. FM, ATEX and CE approvals.

Configure

$2,751.05 
SS4-A2
(1992)

HONEYWELL  SS4-A2

Honeywell Fire Sentry SS4-A2 UV and UV/IR Electro-Optical Digital Fire and Flame Detector for Hydrocarbon based fires. Alarm and Fault relays, aluminum enclosure. FM certification for Class I, Div 1, Groups B, C & D. Multi-Spectrum. Includes explosion-proof housing.

Configure

$4,104.98 
SS4-AS2
(1993)

HONEYWELL  SS4-AS2

Honeywell Fire Sentry SS4-AS2 UV and UV/IR Electro-Optical Digital Fire and Flame Detector for Hydrogen (H2) and Non-Hydrocarbon based fires. Alarm and Fault relays, aluminum enclosure. FM certification for Class I, Div 1, Groups B, C & D. Multi-Spectrum. Includes explosion-proof housing.

Configure

$5,649.87