| GENERAL SPECIFICATIONS                    | 
| Spectral  Response |  Single band IR 4.4-4.6 μm | 
  Detection  Range (at highest Sensitivity Setting for 1ft2 (0.1m2) pan fire) | 
  	
    	
        	| Fuel | 
            ft / m | 
         
    	
        	| n-Heptane | 
            50 / 15 | 
         
        
        	| Gasoline | 
            50 / 15 | 
         
        
        	| Diesel Fuel | 
            37 / 11 | 
         
        
        	| JP5 | 
            37 / 11 | 
         
        
        	| Kerosene | 
            37 / 11 | 
         
        
        	| Ethanol 95% | 
            25 / 7.5 | 
         
        
        	| Methanol | 
            25 / 7.5 | 
         
        
        	| IPA (Isopropyl Alcohol | 
            25 / 7.5 | 
         
        
        	| Hydrogen** | 
            16/5 | 
         
        
        	| Methane* | 
            16 / 5 | 
         
        
        	| LPG * | 
            16 / 5 | 
         
        
        	| Polypropylene Pellets | 
            10 / 3 | 
         
        
        	| Office Paper | 
            20 / 6 | 
         
        
        	* 20" (0.5m) high, 8" (0.2m) width plume fire           	  ** 40/40L/LB only | 
         
     
   | 
| Response  Time | 
 Typically 5 seconds. 
  | 
| Adjustable Time Delay |  Up to 30 seconds                 
  | 
| Sensitivity Ranges |  2 ranges; 1 ft2 (0.1m2) n-heptane pan fire from 15 ft (5m) or 50 ft (15m)
  | 
| Field of View |  Horizontal 90º; Vertical 90º
  | 
| Built-in-Test (BIT) |  Automatic (and Manual)                 
  | 
| Temperature Range |  Operating: -67ºF to +167ºF      (-55ºC to +75ºC)             Option: -67ºF to +185ºF      (-55ºC to +85ºC)             Storage: -67ºF to +185ºF      (-55ºC to +85ºC)          
  | 
| Humidity |  Up to 95%  non-condensing (withstands up to 100% RH for short periods)                 
  | 
| Heated  Optics |  To eliminate condensation and icing on the window                 
  | 
| ELECTRICAL SPECIFICATIONS                    | 
| Operating Voltage |  24 VDC nominal (18-32 VDC)                 
  | 
| Power  Consumption | Standby: Max. 90mA (110mA with heated window) 
  Alarm: Max. 130mA (160mA with heated window)
  | 
| Cable  Entries |  2 x 3/4" - 14NPT conduits or 2 x M25 x 1.5 mm ISO                 
  | 
| Wiring |  12 - 22AWG   (2.5mm   2 - 0.3mm 2)            
  | 
| Electrical Input Protection |  According to  MIL-STD-1275B                 
  | 
| Electromagnetic  Compatibility |  EMI/RFI protected to EN50130-4                 
  | 
| Electrical Interface |  The detector includes twelve (12) terminals with five (5) wiring options (factory set)                 
  | 
| OUTPUTS                    | 
| Relays |  Alarm, Fault and Auxiliary                    SPST volt-free contacts rated  5A at 30 VDC or 250 VAC.                 
  | 
| 0-20mA  (stepped) |  Sink (source option) configuration 
  Fault: 0 +1mA 
  BIT Fault: 2mA ± 10% 
  Normal: 4mA ± 10%  
  Warning: 16mA ± 5% 
  Alarm: 20mA ± 5% 
  Resistance Loop: 100-600 Ω | 
| HART  Protocol | 
   Optional HART communication on the 0-20mA analog current (FSK) - used for maintenance, configuration  changes and asset management                 
  | 
| RS-485 |  RS-485 Modbus compatible communication  link that can be used in computer controlled                    installations                 
  | 
| MECHANICAL SPECIFICATIONS                    | 
Materials Enclosure options |  - Stainless Steel 316L with electro polish finish - Heavy duty copper free aluminum (less than 1%), red epoxy enamel finish  | 
| Mounting |  Stainless Steel 316L with electro polish  finish                 
  | 
| Dimensions |  Detector     3.5" x 4.5" x 6.1"   (90  x 114 x 156 mm)         
  | 
| Weight |  Detector (St.St.)     5.5 lb (2.5 kg)              Detector, aluminum     2.5 lb (1.2 kg)              Tilt mount     2.2 lb (1.0 kg)           
  | 
| Environmental Standards |  Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp                 
  | 
| Water  and Dust |  IP66 and IP67 per EN60529, NEMA 250 6P                 
  | 
| APPROVALS                    | 
| Hazardous Area | 
		
        	
            	| ATEX and IECEx | 
                Ex II 2 GD, | 
                  | 
             
            
            	|   | 
                Ex de IIB+H2 T5 o (-5+55 ºCºC 7 | 
                x de IIB+H2 T4 (-55ºC to + 85ºC) | 
             
            
            	|   | 
                Ex tD A21 IP66/X7 T 95ºC | 
                Ex tD A21 IP66/X7 T 105ºC | 
             
            
            	| FM / CSA | 
                Class I Div. 1, Groups B, C & D | 
                  | 
             
            
            	|   | 
                Class II/III Div. 1, Groups E, F & G | 
                  | 
             
         
	 | 
| Performance |  EN54-10 (LPCB)                    FM-3260  (FM)                 
  | 
| Reliability |  IEC61508 - SIL2 (TUV)                 
  | 
| ACCESSORIES                    | 
| Fire Simulator | 20/20-312
  | 
  | Weather Protector | 777163 | 
  Laser Pointer (Detector area coverage) | 777166 | 
  | Tilt Mount | 
  40/40-001 | 
| Air Shield | 777161 |