The XP10-M ten-input monitor module is an interface
between a control panel and normally open contact devices
in intelligent alarm systems such as pull stations, security
contacts, or flow switches.
The first address on the XP10-M is set from 01 to 150 and
the remaining modules are automatically assigned to the
next nine higher addresses. Provisions are included for dis-
abling a maximum of two unused addresses.
The supervised state (normal, open, or short) of the moni-
tored device is sent back to the panel. A common SLC input
is used for all modules, and the initiating device loops share a
common supervisory supply and ground — otherwise each
monitor operates independently from the others.
Each XP10-M module has panel-controlled green LED indi-
cators. The panel can cause the LEDs to blink, latch on, or
latch off.
NOTE: Unless otherwise specified, the term XP10-M is used in
this data sheet to refer to both the XP10-M and the XP10-MA
(ULC-listed version) .
FEATURES
- Listed to UL Standard 864, 9th edition.
- Ten addressable Class B or five addressable Class A initi-
ating device circuits.
- Removable 12 AWG (3.31 mm2) to 18 AWG (0.821 mm2)
plug-in terminal blocks.
- Status indicators for each point.
- Unused addresses may be disabled.
- Rotary address switches.
- Class A or Class B operation.
- FlashScan® or CLIP operation.
- Flexible mounting options.
- Mounting hardware included.
Agency Listings and Approvals
The listings and approvals below apply to the XP10-M(A) Ten-
Input Monitor Module. In some cases, certain modules or
applications may not be listed by certain approval agencies, or
listing may be in process. Consult factory for latest listing
status.
- UL Listed: S635
- CSFM approved: 7300-0028:219
- FM approved
- ULC Listed: S635 (XP10-MA)
- MEA approved: 43-02-E
- Maryland State Fire Marshal approved: Permit #2106