NOTIFIER by Honeywell ONYX Series NFS-320 Intelligent Addressable Fire Alarm Control Panel. Certified for seismic and marine applications. Supports up to 159 detectors and 159 modules. Standard 80-character display and 6A power supply. Built-in Alarm, Trouble, Security and Supervisory relays, FlashScan network prototol. *** UNPREDICTABLE LEAD TIME ****

NFS-320   
Please Email us your request for quote   

Version
Digital Input
Digital Output
Digital Output
Language

   26 Weeks  ]


The NFS-320 intelligent Fire Alarm Control Panel is part of the ONYX® Series of Fire Alarm Controls from NOTIFIER.

In stand-alone or network configurations, ONYX Series products meet virtually every application requirement.

The NFS-320’s modular design makes system planning easier. The panel can be configured with just a few devices for small building applications, or networked with many devices to pro- tect a large campus or a high-rise office block. Simply add additional peripheral equipment to suit the application.

For installations using NFS-320C, an optional ACM Series annunciator can be mounted in the same cabinet (up to 48 zones/points, order separately; see DN-60085).

The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet, saving the monthly cost of two dedicated business tele- phone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line.

NOTE: Unless called out with a version-specific “R”, “C” or “E” at the end of the part number, “NFS-320” refers to models NFS-320, NFS-320R, NFS-320C, and NFS-320E.

NFS-320 FEATURES

  • Certified for seismic applications when used with the appro- priate seismic mounting kit.
  • Approved for Marine applications when used with listed compatible equipment (see DN-60688).
  • One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7.
  • Up to 159 detectors (any mix of ion, photo, thermal, or multi- sensor) and 159 modules (Addressable pull stations, nor- mally open contact devices, two-wire smoke, notification, or relay). 318 devices maximum.
  • Standard 80-character display.
  • Network options:
    • High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC, ONYXWorks, NFS-3030, NFS-640, and NCA).
    • Standard network for up to 103 nodes (NFS2-3030, NFS2- 640, NFS-320(C), NFS-320SYS, NCA-2, DVC, ONYX- Works, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP- 300/400, AFP-1010, and AM2020). Up to 54 nodes when DVC is used in network paging.
  • 6.0 A power supply with four Class A/B built-in Notification Appliance Circuits (NAC). Selectable System Sensor, Wheelock, or Gentex strobe synchronization.
  • Built-in Alarm, Trouble, Security, and Supervisory relays.
  • VeriFire® Tools online or offline programming utility. Upload/ Download, save, store, check, compare, and simulate panel databases. Upgrade panel firmware.
  • Autoprogramming and Walk Test reports.
  • Optional universal 318-point DACT.
  • 80-character remote annunciators (up to 32).
  • EIA-485 annunciators, including custom graphics.
  • Printer interface (80-column and 40-column printers).
  • History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm-only file.
  • Alarm Verification selection per point, with tally.
  • Presignal/Positive Alarm Sequence (PAS).
  • Silence inhibit and Auto Silence timer options.
  • NAC coding functions:
    • March time.
    • Temporal.
    • California two-stage coding.
    • Canadian two-stage.
    • Strobe synchronization.
  • Field-programmable on panel or on PC, with VeriFire® Tools program check, compare, simulate.
  • Full QWERTY keypad.
  • Battery charger supports 18 – 200 AH batteries.
  • Non-alarm points for lower priority functions.
  • Remote ACK/Signal Silence/System Reset/Drill via monitor modules.
  • Automatic time control functions, with holiday exceptions.
  • Extensive, built-in transient protection.
  • Powerful Boolean logic equations.
FLASHSCAN® INTELLIGENT FEATURES

  • Poll up to 318 devices in less than two seconds.
  • Activate up to 159 outputs in less than five seconds.
  • Multicolor LEDs blink device address during Walk Test.
  • Fully digital, high-precision protocol (U.S. Patent 5,539,389).
  • Manual sensitivity adjustment — nine levels.
  • Pre-alarm ONYX intelligent sensing — nine levels.
  • Day/Night automatic sensitivity adjustment.
  • Sensitivity windows:
    • Ion – 0.5 to 2.5%/foot obscuration.
    • Photo – 0.5 to 2.35%/foot obscuration.
    • Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
    • Acclimate® PlusTM – 0.5 to 4.0%/foot obscuration.
    • IntelliQuad – 1.0 to 4.0%/foot obscuration.
    • IntelliQuadTM PLUS – 1.0 to 4.0%/foot obscuration
  • Drift compensation (U.S. Patent 5,764,142).
  • Degraded mode — in the unlikely event that the NFS-320’s primary microprocessor fails, FlashScan detectors revert to degraded operation and can activate the control panel’s NAC circuits and alarm relay. Each of the four built-in panel circuits includes a Disable/Enable switch for this feature.
  • Multi-detector algorithm involves nearby detectors in alarm decision (U.S. Patent 5,627,515).
  • Automatic detector sensitivity testing (NFPA-72 compliant).
  • Maintenance alert (two levels).
  • Self-optimizing pre-alarm.
FSL-751 VIEW (VERY INTELLIGENT EARLY WARNING) SMOKE DETECTION TECHNOLOGY

  • Revolutionary spot laser design.
  • Advanced ONYX intelligent sensing algorithms differentiate between smoke and non-smoke signals (U.S. Patent 5,831,524).
  • Addressable operation pinpoints the fire location.
  • No moving parts to fail or filters to change.
  • Early warning performance comparable to the best aspiration systems at a fraction of the lifetime cost.
FAPT-851 ACCLIMATE® PLUSTM LOW-PROFILE INTELLIGENT MULTI-SENSOR

  • Detector automatically adjusts sensitivity levels without oper- ator intervention or programming. Sensitivity increases with heat.
  • Microprocessor-based technology; combination photo and thermal technology.
  • FlashScan or CLIP (“classic”) mode compatible.
  • Low-temperature warning signal at 40°F ± 5°F (4.44°C ± 2.77°C).
FSC-851 INTELLIQUAD ADVANCED MULTI-CRITERIA DETECTOR

  • Detects all four major elements of a fire (smoke, heat, CO, and flame).
  • Automatic drift compensation of smoke sensor and CO cell.
  • High nuisance-alarm immunity.
  • Six sensitivity levels.
FCO-851 INTELLIQUADTM PLUS ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR

  • Detects all four major elements of a fire.
  • Separate signal for life-safety CO detection.
  • Optional addressable sounder base for Temp-3 (fire) or Temp-4(CO) tone.
  • Automatic drift compensation of smoke sensor and CO cell.
  • High nuisance-alarm immunity.
  • Six sensitivity levels.
RELEASING FEATURES

  • Ten independent hazards.
  • Sophisticated cross-zone (three options).
  • Delay timer and Discharge timers (adjustable).
  • Abort (four options).
  • Low-pressure CO2 listed
VOICE FEATURES

  • Integrates with FireVoice-25/50 Series (see DN-7004).
  • Integrates via serial connection with FireVoice-25/50ZS Series (see DN-7003).
HIGH-EFFICIENCY OFFLINE SWITCHING 3.0 A POWER SUPPLY (6.0 A IN ALARM)

  • 120 VAC (NFS-320/NFS-320C); 240 VAC (NFS-320E).
  • Displays battery current/voltage on panel (with display).
System Capacity

  • Intelligent Signaling Line Circuits: 1
  • Intelligent detectors: 159
  • Addressable monitor/control modules: 159
  • Programmable internal hardware and output circuits: 4
  • Programmable software zones: 99
  • Special programming zones: 14
  • LCD annunciators per NFS-320/-320E: 32
  • ACS annunciators per NFS-320/-320E: 32 addresses x 64 points
Temperature and Humidity Ranges

This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme tempera- ture ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.

Agency Listings and Approvals

The listings and approvals below apply to the basic NFS-320 control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Con- sult factory for latest listing status.

  • UL Listed: S635.
  • ULC Listed: S635 (NFS-320C only, excludes IPDACT).
  • FM Approved.
  • CSFM: 7165-0028:0243.
  • MEA: 128-07-E.
  • FDNY: COA#6085.
  • City of Chicago.

When used with the CAB-BM marine system, appropriate seis- mic bracket, and marine approved devices, these ONYX fire alarm control panels are approved by the following agencies:

  • US Coast Guard: 161.002/50/0 (Standard 46 CFR).
  • Lloyd's Register: 11/600013 (ENV 3 category).
  • American Bureau of Shipping.

NOTE: For additional information on UL- and ULC-listed model NFS-320C, see DN-60085. For information on NFS-320SYS, see DN-60637. For information on the CAB-BM marine system, see DN-60688.

Standards

The NFS-320 complies with the following UL Standards and NFPA 72, IBC, and CBC Fire Alarm Systems requirements:

  • UL 864 (Fire).
  • UL 1076 (Burglary).
  • LOCAL (Automatic, Manual, Waterflow and Sprinkler Super-visory).
  • AUXILIARY (Automatic, Manual and Waterflow) (requiresTM-4).
  • REMOTE STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) (requires TM-4).
  • PROPRIETARY (Automatic, Manual, Waterflow and Sprinkler Supervisory). Not applicable for FM.
  • CENTRAL STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) (requires UDACT).
  • EMERGENCY VOICE/ALARM.
  • OT, PSDN (Other Technologies, Packet-switched Data Net-work).
  • IBC 2000, IBC 2003, IBC 2006, IBC2009 (Seismic).
  • CBC 2007 (Seismic).

NFS-320 SPECIFICATIONS
Primary input power NFS-320: 120 VAC, 50/60 Hz, 5.0 A.
NFS-320E: 220/240 VAC, 50/60 Hz, 2.5 A.
Total output 24 V power 6.0 A in alarm.
Standard notification circuits: 4x1.5 A
Resettable regulated 24V power: 1.25A
Two non-resettable regulated 24V power outputs 1.25A
0.50A
Non-resettable 5V power: 0.15 A.
Battery charger range: 18 AH – 200 AH. Use separate cabi- net for batteries over 26 AH.
Float rate: 27.6 V
NFS-320 CABINET SPECIFICATIONS
Backbox: 18.12 in. (46.025 cm) width; 18.12 in. (46.025 cm) height; 5.81 in. (14.76 cm) depth.
Door: 18.187 in. (46.195 cm) width; 18.40 in. (46.736 cm) height; 0.75 in. (1.905 cm) depth.
Trim ring: Molding width is 0.905 in. (2.299 cm).
Shipping weight (without batteries): 36.15 lb. (16.4 kg).
Export Info
Made inUnited States

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> ACCESSORIES - RELATED - CONSUMABLES :    11 Items found.
FST-951
(3228)

NOTIFIER  FST-951

Notifier FST-951 Series Intelligent Addressable Thermal (Heat) Detector with FlashScan and CLIP protocol systems. Two-wire SLC connection and 360° viewing angle. Optional relay, isolator and sounder bases. UL/ULC Listing. FM, and CSFM Approved. *** Replaces FST-851 ***

FMM-1
(3695)

NOTIFIER  FMM-1

Notifier FMM-1/FMM-101 Series Monitor Module for supervised dry-contact input devices or monitor and power two-wire circuits. Two-wire SLC loop. High noise immunity. 15 to 32 VDC. UL, FM, CSFM, MEA and US Coast Guard Approved.

FSP-951
(2038)

NOTIFIER  FSP-951

NOTIFIER by Honeywell FSP-951 Series Intelligent Plug-in Photoelectric Smoke Detector (0.5% to 4% per foot obscuration) with FlashScan and CLIP communication protocol systems. Addressable-analog communication. Optional relay, isolator and sounder bases. UL, ULC, FM and CSFM Approvals. *** Replaces FSP-851 ***

FRM-1
(3694)

NOTIFIER  FRM-1

Notifier FRM-1 Series Relay Module for activation of auxiliary devices (fans, dampers, etc). Two-wire SLC loop. Two Form-C dry contacts. High noise immunity. 15 to 32 VDC. UL, FM, CSFM, MEA and FDNY Approved.



 
FCM-1
(3236)

NOTIFIER  FCM-1

Notifier FCM-1 Series Addressable Control Module for Notification Appliances (horns, strobes, speakers, etc). Two-wire SLC loop. High noise immunity. 15 to 32 VDC. UL, FM, CSFM, MEA and FDNY Approved.



 
NBG-12LX
(2042)

NOTIFIER  NBG-12LX

NOTIFIER by Honeywell NBG-12LX Addressable Manual Pull Station, dual-action (requires two motions to activate the station) pull station that includes an addressable interface for any Notifier intelligent control panel.

FCO-951
(3502)

NOTIFIER  FCO-951

Notifier IntelliQuad® PLUS FCO-951 Advanced Multi-Criteria Fire/CO Detector with four unique sensing elements: Carbon Monoxide (CO) electrochemical sensor, Infrared (IR) sensing measure, Photo-electric smoke detection and Thermal detection. UL listed. *** replaces FSC-851 ***



 
FSV-951R
(3229)

NOTIFIER  FSV-951R

Notifier FSV-951R Series Very Intelligent Plug-in Early Warning (VIEW®) Laser Smoke Detector. 0.03% to 1.00% (CLIP) or 0.02% to 2.00% (other) sensivity. With FlashScan and CLIP protocol systems. Advanced laser light source and 360° viewing angle. Optional relay, isolator and sounder bases. UL and MEA listed. FM, CSFM, BSMI and CCCF Approved. (replaces FSL-751)

XP10-M
(3724)

NOTIFIER  XP10-M

Notifier XP10-M Ten Input Monitor Module for intelligent alarm systems. Up to 10 addresable Class B or 5 addressable Class A devices. SLC inputs. Green LED indicators. Flexible mounting options. FlashScan® or CLIP operation. UL Listed. CSFM, FM, MEA and MSTM approved.



 
ACPS-610
(6936)

NOTIFIER  ACPS-610

Notifier ACPS-610 Addressable Charger/Power Supply. Provides 6 amps of shared power to four outputs or 10 amps as an external battery charger. SLC circuit. UL, ULC, CSFM and FM listed.

HS-NCM-MF__
(4326)

NOTIFIER  HS-NCM-MF

Notifier HS-NCM High-Speed Network Communications Module. Single or Multi-mode versions available. Allow connection from Notifier Panels to NOTI•FIRE•NET™ with a fiber-optic cable or twisted-pair wire. NFPA Style 4 (Class B) or Style 7 (Class A) operation. 24 VDC, 100Mb baud transmission rate. UL, ULC, CSFM and FM approved.

> SMOKE THERMAL IONIZATION :    1 Items found.
RP-2001
(6945)

NOTIFIER  RP-2001

Notifier RP-2001 Deluge/Preaction six-zone Control Panel for single and dual hazard applications. 4 outputs for NACs or releasing circuits. Three programmable Form-C relays and 24 VDC resettable and non-resettable power outputs. 120 VAC and 240 VAC versions. LCD display. UL, FM and CSFM Approved.

Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.