SPECTREX   40/40U-111AF

SPECTREX 40/40U_-111AF
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
SPECTREX SharpEye 40/40U UV-Based Fast Response Flame Detector detects hydrocarbon-based fuel and gas fires, invisible hydrogen flames, and fires from hydrides, ammonia, silane and other organics, 200 msec response to flash fire. 3 Relays (Alarm, Fault and Auxiliary), 0-20mA stepped, compatible with RS-485 Modbus. SIL2 (TUV) approved to IEC 61508. Built-in-test (BIT) optional. Ex approved for Zone 1, ATEX, IECEx, FM and CSA Class I Div 1. 5 year warranty and is SIL2 (TUV) approved to IEC 61508 *** Phased Out ***

Inquiry

For special applications with little direct sunlight and no halogen lamps.

The 40/40U-UB is the most durable and weather resistant UV flame detector currently on the market. Its new features include a heated window, to eliminate condensation and icing; HART capabilities, for digital communications; lower power requirements; and a compact, lighter design.

Due to increased reliability, the 40/40 Series warranty period has been extended to 5 years and is SIL2 (TUV) approved to IEC 61508.

The model 40/40UB includes a Built-in-Test (BIT) feature, whereas the 40/40U model does not.

Note: This type of detector should not be exposed to UV radiation sources such as welding, sparks, and electric arcs as it will cause false alarms.

Features
  • UV spectrum design
  • 3 seconds response
  • Automatic and Manual Built-In-Test (BIT) - to assure continued reliable operation
  • Heated window - for operation in harsh weather conditions (snow, ice, condensation)
  • Multiple output options for maximum flexibility and compatibility
    • Relays (3) for Alarm, Fault and Auxiliary
    • 0-20mA (stepped)
    • HART Protocol for maintenance and asset management
    • RS-485, Modbus Compatible
  • High Reliability - MTBF - minimum 150,000 hours
  • Approved to Safety Integrity Level 2 (SIL2 – TUV) Model 40/40UB only
  • 5-Year Warranty
  • User Programmable via HART or RS-485
  • Ex approved for Zone 1 hazardous area location
    • ATEX
    • IECEx
    • FM/FMC
    • CSA
  • 3rd party Performance Tested
    • EN54-10 (LPCB)
    • FM3260 (FM)
Applications
  • Chemical plants
  • Petrochemicals plants
  • Power Generation facilities
  • Pharmaceutical Industry
  • Printing Industry
  • Warehouses
  • Automotive Industry
  • Aerospace
  • Explosives & Munitions
  • Waste Disposal facilities
  • Paint and solvent processes

GENERAL SPECIFICATIONS
Spectral Response UV 0.185-0.260 μm
Detection Range
(at highest Sensitivity Setting for 1ft2 (0.1m2) pan fire)
Fuel ft / m
n-Heptane 50 / 15
Gasoline 50 / 15
Diesel Fuel 37 / 11
JP5 37 / 11
Kerosene 37 / 11
Ethanol 95% 37 / 11
Methanol 37 / 11
IPA (Isopropyl Alcohol 37 / 11
Hydrogen 33 / 10
Methane* 40 / 12
LPG * 40 / 12
Polypropylene Pellets 18 / 5
Office Paper 20 / 6
* 20" (0.5m) high, 8" (0.2m) width plume fire
Response Time Typically 3 seconds
Adjustable Time Delay Up to 30 seconds
Sensitivity Ranges1 ft2 (0.1m2) n-heptane pan fire from 50 ft (15m)
Field of View Horizontal 100º; Vertical 95º
Built-in-Test (BIT) Automatic (and Manual)
Temperature Range Operating: -67ºF to +167ºF (-55ºC to +75ºC)
Option: -67ºF to +185ºF (-55ºC to +85ºC)
Storage: -67ºF to +185ºF (-55ºC to +85ºC)
Humidity Up to 95% non-condensing (withstands up to 100% RH for short periods)
Heated Optics To eliminate condensation and icing on the window
ELECTRICAL SPECIFICATIONS
Operating Voltage 24 VDC nominal (18-32 VDC)
Power Consumption Standby: Max. 90mA (110mA with heated window)
Alarm: Max. 130mA (160mA with heated window)
Cable Entries 2 x 3/4" - 14NPT conduits or 2 x M25 x 1.5 mm ISO
Wiring 12 - 22AWG (2.5mm 2 - 0.3mm 2)
Electrical Input Protection According to MIL-STD-1275B
Electromagnetic Compatibility EMI/RFI protected to EN61326-3 and EN61000-6-3
Electrical Interface The detector includes twelve (12) terminals with five (5) wiring options (factory set)
OUTPUTS
Relays Alarm, Fault and Auxiliary
SPST volt-free contacts rated 5A at 30 VDC or 250 VAC.
0-20mA (stepped) Sink (source option) configuration
Fault: 0 +1mA
BIT Fault: 2mA ± 10%
Normal: 4mA ± 10%
Warning: 16mA ± 5%
Alarm: 20mA ± 5%
Resistance Loop: 100-600 Ω
HART Protocol Optional HART communications on the 0-20mA analog current (FSK) - used for maintenance, configuration changes and asset management, available in mA source output wiring options
RS-485 RS-485 Modbus compatible communication link that can be used in computer controlled
installations
MECHANICAL SPECIFICATIONS
Materials
Enclosure options
- Stainless Steel 316L with electro polish finish
- Heavy duty copper free aluminum (less than 1%), red epoxy enamel finish
Mounting Stainless Steel 316L with electro polish finish
Dimensions Detector 4" x 4.6" x 6.18" (101.6 x 117 x 157 mm)
Weight Detector (St.St.): 6.1 lb (2.8 kg)
Detector, aluminum: 2.8 lb (1.3 kg)
Tilt mount: 2.2 lb (1.0 kg)
Environmental StandardsMeets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp
Water and Dust IP66 and IP67 per EN60529, NEMA 250 6P
APPROVALS
Hazardous Area
ATEX and IECEx Ex II 2 GD,  
  Ex de IIC T5 (-55oC to +75oC) Ex de IIC T4 (-55oC to +85oC)
  Ex tD A21 IP66/X7 T 95oC Ex tD A21 IP66/X7 T 105oC
FM / FMC / CSA Class I Div. 1, Groups B, C & D  
  Class II/III Div. 1, Groups E, F & G  
Performance EN54-10 (LPCB)
FM-3260 (FM)
Reliability IEC61508 - SIL2 (TUV) - model 40/40UB only
ACCESSORIES
Fire Simulator20/20-311
U-Bolt/Pole Mount 789260-2 (2" pole)
789260-1 (3" pole)
Mini Laptop Kit 777820
Laser Pointer777166
Tilt Mount40/40-003
Weather Protector777163
Duct Mount777670
USB RS485 Harness Kit794079-5
Air Shield777161
Export Info
Made inUnited States
Harmonized Tariff Code (HTC)90318099
> ACCESSORIES - RELATED - CONSUMABLES :    4 Items found.
(3484)

SPECTREX  789260-2

Pole mount (U-bolt) - 2" for SPECTREX SharpEye flame detectors (does not include required 40/40-001 tilt mount)



$274.84 
794079-5
(3149)

SPECTREX  794079-5

USB RS485 Harness Kit with RS485/232 converter, used with Spectrex Host software, enables the user to connect to any available PC or laptop to re-configure settings or perform diagnostics on all 40/40 and 20/20 series flame detectors. Includes Host Software.

Configure

$487.19 
FS-1200
(902)

SPECTREX  FS-1200

SPECTREX FS-1200 Long range flame simulator test lamp for all Spectrex UV and UV/IR Flame Detectors. Approved for Zone 1 and Zone 2 hazardous areas. Up to 26ft testing distance. Includes rechargeable Lithium-ion battery, charger, built-in beam collimator, tool kit and user guide in carrying case. IP65. ATEX and IECEx approved. (Replaces 20/20-311)



$6,190.21 
888810
(3482)

SPECTREX  888810

Emerson HART Hand-Held Diagnostics Unit c/w converter and cable harness (1m), software and manual in case. For SPECTREX SharpEye flame detectors and Quasar 900 gas detectors, certified I.S. (EExia)



$13,376.70 
> ULTRAVIOLET :    2 Items found.
100-0003-01
(4718)

ESP SAFETY  100-0003-01

ESP Safety IPES-UV Ultraviolet Flame Detector of hydrogen, metal fire and pyrophoric material fires. 180 to 250 nanometers range. 90 degree field of view. RS-485, Modbus RTU, 4-20mA and relay outputs. Color status LED. Explosion-proof. Designed for Class I, Division 1, Group B, C & D. ATEX certified, SIL3 Rated. Includes protective visor, stainless steel mounting bracket and hardware.

Configure

$1,350.00 
FSL100-UV
(6770)

HONEYWELL  FSL100-UV

Honeywell FSL100-UV Flame Detector for robust, fast, and reliable detection of hydrocarbon or hydrogen fires in indoor/outdoor environments and potentially explosive atmospheres. Relay and mA outputs. GRP housing. EN54-10 and FM3260 approvals. IP65.

Configure

$2,433.66 
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.