The Honeywell HPFF8(E) and HPFF8CM(E) are Notification
Appliance Circuit (NAC) Expander Power Supplies designed to
extend the power capabilities of existing NACs and provide
power for auxiliary devices. The HPFF8 and HPFF8CM connects to any 12 or 24V Fire Alarm Control Panel (FACP) or
operates stand-alone.
They provide regulated and filtered 24VDC power to four
NAC's and an auxiliary output. The NAC outputs are rated at
3.0 amps each and the auxiliary output is rated at 2.0 amps
(this output is continuously supplied, even in alarm, and therefore must be taken into account for power supply loading and
battery size calculations). The combined output cannot exceed
8.0 amps.
The HPFF8 and HPFF8CM provide independent output circuit
supervision so in the event of a NAC fault they can notify the
attached FACP. In addition they have a trouble memory feature that displays past troubles (by NAC) for rapid diagnostics.
Synchronization is built in for five appliance brands.
The HPFF8 and HPFF8CM have two fully independent supervised initiating circuits that can be used for synchronized
strobes and coded horns. Their NAC outputs may be configured as any of the following:
- four Class B (Style Y)
- two Class A (Style Z)
- two Class B and one Class A
- four Class A with the optional HPP31076 Class A adapter
These power supplies contain an internal Battery charger
capable of charging up to 26.0 amp-hour (AH) batteries.
The HPFF8 is mounted in a lockable wall cabinet that can
accommodate up to two 18AH batteries. The HPFF8CM is
designed to mount in Notifier’s large CAB-4 series or equipment series enclosure (order separately). Each HPFF8CM can
accommodate two 12AH batteries.
One of the most challenging aspects of a retrofit application is
locating the existing End-of-Line (EOL) resistor. In these applications that have EOL values other than the 3.9k normally
used with the HPFF8, a single resistor matching the existing
EOL can be used as a reference for all the outputs. This feature speeds installation and system checkout because the
actual EOL does not need to be located and changed in the
circuit. The reference resistor must be within the range of 1.9k
to 25k.
NOTE: 4 separate programming resistors for the HPFF8 are provided in the hardware kit shipped with each HPFF8(E) and
HPFF8CM(E). They are 3.9K (5 of these are provided, need only
1 for programming), 2.2K (1 each), 4.7K (1 each) and 10K (1 each)
Features
- Four (4) power limited supervised notification application circuits (NAC's) capable of supplying +24VDC at 3.0 amp maximum each.
- NAC output circuits may be configured as any of the following:
- Four Class B (Style Y).
- Two Class B & one Class A.
- Two Class A (Style Z).
- Four Class A (requires the HPP31076 Class A adapter).
- Four field-programmable operational modes:
- Pass-through.
- Temporal generator.
- Sync generator.
- Pass-through Filtered.
- Temporal coding and sync protocols compatible with the following notification appliance brands:
- System Sensor.
- Faraday.
- Amseco.
- Cooper-Wheelock.
- Gentex.
- Protocol pass-through for synchronizing large systems.
- Two fully independent supervised input/output control circuits.
- Redundant activation operation for survivability.
- Supports FACP’s Selectable Silence ability.
- 2.0 amp auxiliary continuously supplied output.
- Eight status LEDs.
- Supervised AC input, battery voltage, auxiliary output, charger, and earth ground faults.
- Trouble indication for supervision of the following:
- NAC circuits.
- Auxiliary output.
- AC input.
- Battery charger voltage.
- Earth ground faults.
- Optional two-hour delay for AC loss.
- Separate Trouble and AC Fail Form-C relay contacts.
- The Trouble Form-C relay contacts selectable for immediate or a 2 hour delay with AC failure.
- 26 AH battery charger capability:
- HPFF8(E) supports two 12V 18AH batteries
- HPFF8CM(E) supports two 12V 12AH batteries per unit.
- NAC Overload protection and indication.
- Provision for mounting single or 6 circuit addressable control or relay modules inside the enclosure. (Use mounting kit PN 90475.)
- Standard Honeywell key and lock can be replaced with the NOTIFIER key and lock.
Listings and Approvals
Listings and approvals below apply to all. In some cases, certain modules may not be listed by certain approval agencies,
or listing may be in process. UL 864 9th Edition.
- UL Listed: S24562
- Seismic Certification of Non-Structural Electrical Components and Systems
- FM Approved
- CSFM: 7315-1637:0102
- NYFD: COA#6032