The Network Control Display (NCD) is the next generation of network control annunciators for the NOTI•FIRE•NETTM network. Its
contemporary design meets today’s building aesthetics. The intuitive
1024 x 600 10" touch screen provides detailed color coded system
status and point information. It is compatible with NOTIFIER
INSPIRETM and ONYX® series fire alarm control panels (FACP) and
nodes such as the INSPIRE N16e/x FACPs, ACM-30 annunciator
and RLD remote display as well as the ONYX NFS2-3030, NFS2-640, and NFS-320 FACPs.
The NCD provides system control and status/history display capabilities for all, or for selected network nodes. It can also be used as the
primary display for control and status capabilities on a displayless
node via Direct Connect.
Hardware Features
- Full supervision of all inputs and network integrity.
- High definition 10" 1024 x 600 color touchscreen display.
- LED status indicators for power and off normal
- Requires 24 VDC, and a network connection or direct connect.
- Three USB 2.0 connections, USB C, USB Micro, and USB A.
- Trouble Relay.
- Tamper and Trouble inputs.
Function Features
- Device information, including point address and description, can be quickly identified.
- Network-wide: Acknowledge, Silence, Reset.
- Lamp Test.
- Interactive Summary Event Count display and event handling.
- Intuitive user guidance program.
- Fully programmable node-mapping subsystem.
- Up to 2000 programmable logic zones
- Up to 32 custom action buttons
- Environmental adjustment controls to maximize display legibility.
- Color coded Icon based event notification.
- Can be used as FACP primary display.
- Supports standard and high speed network systems.
- Event vectoring for quick viewing of event groups.
- Virtual alphanumeric QWERTY keypad and numeric keypad displays when data input is needed.
- Individual Enable/Disable or group Enable/Disable for networked ONYX and INSPIRE series panels.
- Control ON/OFF for networked ONYX and INSPIRE series panel control points.
- Read Status networked ONYX and INSPIRE series panel points and zones.
- History Buffer (10,000 events, 3000 displayed).
- Up to 50 unique users and 5 different user levels.
- Read Status from event display.
- History filters for report displaying.
- Timer control for Auto Silence, AC Fail Delay.
- Custom wallpaper
NCD Indicators and Controls
LED INDICATORS
Green LED illuminates when 24 VDC power is applied; When on
battery backup, the green LED will not illuminate.
Yellow LED illuminates when an off normal condition exists.
VIRTUAL EVENT INDICATORS
- FIRE ALARM (red) illuminates when at least one fire alarm event exists.
- CO Alarm (blue) illuminates when at least one CO alarm event exists.
- SUPERVISORY (yellow) illuminates when at least one supervisory event exists (i.e., sprinkler valve off normal, low pressure, fire pump running, guard’s tour, etc.).
- TROUBLE (yellow) illuminates when at least one trouble event exists.
- POINT DISABLED (yellow) illuminates when at least one disable exists on the network or in the system.
- OTHER (varies) illuminates for SECURITY, PRE-ALARM, CO PRE-ALARM, and CRITICAL PROCESS.
- SIGNALS SILENCED (yellow) illuminates if the NCD Silence touch point has been pressed or if any other node sent a Network Silence command.
FUNCTION TOUCHPOINTS
- Menu
- Login
- Acknowledge
- Signal Silence
- System Reset
- Drill
Ack (Acknowledge) Tap this touchpoint to acknowledge off all
active events.
Silence (Signal Silence) Tap this touchpoint to turn off all control
modules, notification appliance circuits, and panel output circuits
that have been programmed as Silenceable.
Reset (System Reset) Tap this touchpoint to clear all latched
alarms and other events and clear event indicators.
Drill Hold this touchpoint down for two seconds, to activate all
silenceable output circuits. NOTE: When enabled, the drill touch-
point will be displayed in the Alert Bar.
MENU FUNCTION TOUCHPOINTS
Menu function touchpoints are accessed with the menu dialogs.
- ABOUT – tap this touchpoint to view current firmware and hardware revision numbers.
- DISPLAY – tap this touchpoint to adjust display settings.
- LAMP TEST – tap this touchpoint to test display pixels, LED indicators and piezo.
Agency Listings and Approvals
The file number(s) below reference the specific listings for the modules in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
- UL Listed: S635.
- FM Approved
- CSFM: 7165-0028:0516
- FDNY: COA#001761
Standards and Codes
These listings and approvals below apply to the NCD. In some
cases, certain modules or applications may not be listed by certain
approval agencies, or listing may be in process. Consult factory for
latest listing status.
- UL 864, 10th edition
- NFPA 72 National Fire Protection Association