Detcon FP-700 non-intrusive Smart Sensor designed to detect and monitor combustible gases with range 0-100% LEL using catalytic bead sensor technology. Aluminum or Stainless Steel Junction Box. 4-20mA and Modbus RS-485 outputs. LED Display. Explosion Proof. IP66. CSA, ATEX, CE and SIL2 Approved.

967-521520-100   
Please Email us your request for quote   

Options
Junction Box
Integration Modules
Class 1; Div 1; Groups B, C, D – Zone I Group IIB+H2
Mounting Options
Additional Modules

   3 Weeks  ]
12 Variants of base SKU

Detcon Model FP-700 is a non-intrusive “Smart” sensor designed to detect and monitor combustible gases in air over the range of 0-100% LEL using catalytic bead sensor technology. The plug-in, field replaceable detector is poison-resistant and features over-sized gold-plated connections that help prevent corrosion. The FP-700’s rugged framework includes an electro-polished 316 stainless steel housing with fully encapsulated electronics and dual layer surge protection. This innovative design virtually eliminates sensor failure due to water ingress, corrosion, vibration, and transient spikes. A primary feature of the Model FP-700 is embedded intuitive software that simplifies operator interface by guiding the user through routine calibration, configuration, and fault diagnostic functions using a built-in alpha/numeric display. The Model FP-700 is equipped with standard analog 4-20mA, and ModbusTM RS-485 outputs. Among its unique features is a wireless option that can be used with Detcon’s SmartWireless® product line. Additional integration options include a Remote Alarm Module (RAM), HART, and Foundation Fieldbus. Detcon’s combustible gas sensor has an infinite shelf life and is supported by a 2-year warranty.

Features Failsafe User-Friendly Interface
  • LED Display (With Antiglare Cover)
  • Full Text Display Method
  • Non-intrusive Interface
  • Auto Zero/Auto Span
  • Pre-emptive Fault Diagnostics
Environmentally Bulletproof
  • Electropolished 316SS Construction
  • 100% Epoxy Encapsulated Circuitry
  • Bulletproof I/O Protection
  • Water-Proof, Corrosion-Proof, Vibration-Proof
Modular and Serviceable
  • Modular Design
  • Plug and Play Components
  • Quick Thread Release (For Sensor Replacement)
  • Integral Calibration Port
Applications
  • Oil and Gas Drilling Rigs
  • Oil and Gas Production Sites
  • Offshore Production Platforms
  • FPSOs
  • LNG/CNG Plants
  • Refining and Petrochemical
  • Pulp and Paper Mills
  • Waste Water Treatment Plants

System Specifications
Sensor TypeContinuous diffusion/adsorption
Matched-pair catalytic bead detector
Plug-in field replaceable
Sensor Life3 to 5 years typical
Measurement Range0-100% LEL (lower explosive limit)
Accuracy/Repeatability±3% 0-50% LEL; ±5% 50-100% LEL
Response/Clearing TimeT50 <10 seconds; T90 <30 seconds
Zero Drift<5% per year
OutputsLinear 4-20 mA DC
RS-485 MODBUS-RTU
Electrical ClassificationExplosion proof
CSA and US (NRTL)
Class I, Division 1, Groups B, C, D (Tamb = -40°C to +75°C)
Class I, Zone 1, Group IIB+H2
ATEX
II 2 G Exd IIB + H2 T4 Gb (Tamb = -40°C to +75°C)
Ingress ProtectionNEMA 4X, IP66
Safety ApprovalsCCSAUS Performance to ISA 12.13.01-2000 and CSA 22.2 #152
ATEX
CE Marking
SIL2 Certified to IEC 61508
WarrantyPlug-in detector - 2 years
Transmitter - 2 Years
Environmental Specifications
Operating Temperature Range-40°F to +167°F; -40°C to +75°C
Storage Temperature Range-40°F to +167°F; -40°C to +75°C
Operating Humidity Range0-99% RH non-condensing
Mechanical Specifications
Dimensions7"H x 2.2" Dia.; 178mmH x 65mm Dia. (sensor assembly only)
11"H x 6.1"W x 3.75"D; 280mmH x 155mmW x 96mmD (with junction box)
Mounting holes (J-box) 5.5"; 140mm center to center
Weight2 lbs; 0.907kg (sensor only)
6 lbs; 2.72kg (w/aluminum j-box)
9 lbs; 4.08kg (w/stainless steel j-box)
Electrical Specifications
Power Input11-30 VDC
Power ConsumptionNormal operation = 68mA (<1.7 watt)
Maximum = 85mA (2 watts)
Inrush Current1.0A @ 24V
RFI/EMI ProtectionComplies with EN61000
Analog OutputLinear 4-20mA DC (1,000 ohms max loop load @ 24VDC)
0mA: All Fault Diagnostics
2mA: In-Calibration
4-20mA: 0-100% full-scale
22mA: Over-range condition
Serial RS-485 OutputRS-485 ModbusTM RTU
Baud Rate9600 BPS (9600,N,8,1 Half Duplex)
Status Indicators4-digit LED display with gas concentration
Full-script menu prompts for AutoSpan, Set-up Options, and Fault Reporting
Faults MonitoredOperating Temperature, Loop, Input Voltage, Bridge Voltage, Zero, Sensor, Processor, Memory, Calibration
Cable RequirementsPower/Analog
3-wire shielded cable
Maximum distance is 13,300 feet with 14 AWG
Serial Output
2-wire twisted-pair shielded cable specifically for use with RS-485 installations
Maximum distance is 4,000 feet to last sensor
I/O ProtectionOver-voltage, Miswiring, EMI/RFI Immunity
Export Info
Made inUnited States
Harmonized Tariff Code (HTC)9027102000

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> ACCESSORIES - RELATED - CONSUMABLES :    4 Items found.
943-000000-000
(6566)

DETCON  943-000000-000

Detcon Calibration Sleeve/Wind Guard for use with sensor splash guard for all Detcon sensor heads.



 
(6113)

DETCON  602-003152-000

Detcon bottom housing assembly for FP-700, TP-700 and IR-700. Includes flame arrestor.



 
370-201600-700
(6114)

DETCON  370-201600-700

Detcon Combustible Gas plug-in sensor for FP-700



 
S927-520000-100
(6112)

DETCON  S927-520000-100

Detcon FP-700 Catalytic Combustible Gas ITM (Intelligent Transmitter Module) Spare Part.



 
> LEL CATALYTIC BEAD :    27 Items found.
965-525420-100
(5006)

DETCON  965-525420-100

Detcon MicroSafe FP-524D Smart gas detection Sensor designed to detect and monitor combustible gases with range 0-100% LEL using matched-pair catalytic bead sensor technology. Aluminum Junction Box. 4-20mA output. LED Display. Explosion Proof. IP66. CSA and ISA Approved for Class I, Division 1, Groups B, C, & D.

52001AL-0-9070/100P/L0
(7121)

RC SYSTEMS  52001AL-0-9070/100P/L0

RC Systems SenSmart 5200 3-wire gas detector with Catalytic Bead sensor for Hydrocarbons and Hydrogen (ammonia, butane, ethane, ethanol, hexane, hydrogen, Isopropyl alcohol, pentane, propane, propene, propylene) 0-100% LEL with GEN2 smart sensor, Color backlit LCD Display and 4-20mA output, 10-30 VDC. Aluminum or Stainless Steel enclosure. CSA Class I Division 1 (Explosion-Proof). Optional 2 RS-485 Modbus ports, 2 Programmable Alarm and Fault Relays.

Configure

$1,594.80 
XNXUTAVNNCB1
(852)

HONEYWELL  XNXUTAVNNCB1

Honeywell XNX Universal Gas Detector Transmitter including MPD CATALYTIC BEAD sensor combustible 0-100% LEL (Lower Explosive Limit) Methane (Natural Gas). Backlit LCD Display, HART® over 4-20mA output,UL/CSA approved, 5 x 3/4"NPT entries and painted Aluminum. UL Certified Class 1, Div 1 Groups A, B, C, D / ATEX Zone 1, SIL-2, INMETRO

Configure

$1,728.46 
XCDRFDL
(3004)

HONEYWELL  XCDRFDL

Honeywell Sensepoint XCD RFD (Remote Flammable Detector) Kit. Includes transmitter with LM25, 3/4“NPT Entry, 705 sensor, and 3 wire junction box. Tri-colour backit display. Outputs include 2 programmable alarm relays, 1 programmable fault relay, 4-20mAoutput (sink or source selectable). Sensor can be mounted up to 30 metres (100 feet) from transmitter. cCSAus Certified for North America. Class 1, Div 1, Groups B, C, & D.

Configure

$1,734.98 
966-524520-100
(6100)

DETCON  966-524520-100

Detcon FP-624D Combustible 0-100% LEL Smart Sensor with catalytic bead. Includes detector in stainless steel housing, base connector board, explosion proof enclosure, splashguard, 4-20 mA output, RS-485 serial communication and 3 alarm relays. IP66. CSA approval for Class I, Division 1, Groups C & D.

32001AL-0-9071/100P/L0
(6894)

RC SYSTEMS  32001AL-0-9071/100P/L0

RC Systems SenSmart 3200 3 wire gas detector with Catalytic Bead sensor for Hydrocarbons and Hydrogen (ammonia, butane, ethane, ethanol, hexane, hydrogen, Isopropyl alcohol, pentane, propane, propene, propylene) 0-100% LEL with 'ST-48' smart transmitter. Includes Graphic LCD Display, LED indicator and 4-20mA output, optional alarm relays and Modbus RTU. 10-30 VDC. Aluminum or Stainless Steel enclosure. CSA certified for Class 1 Div 1 (Explosion Proof).

Configure

$1,967.53 
6200AL1-0-109070/100P
(7019)

RC SYSTEMS  6200AL1-0-109070/100P

RC Systems SenSmart 6200 3 wire Dual Channel Gas Detector for Hydrocarbons and Hydrogen Catalytic Bead sensor (acetylene, ammonia, butane, ethane, ethanol, hexane, hydrogen, isopropyl alcohol, methane, pentane, propane, propene or propylene) 0-100% LEL with 'ST-44' smart transmitter and GEN2 smart sensor. Includes Color TFT Display, 4-20mA output. OPTIONAL two RS-485 Modbus ports, embedded Ethernet with Webserver, Modbus TCP, 2 Alarm + Fault Relays. 10-30 VDC. Aluminum, Stainless Steel or Poly enclosure. CSA certified for Class 1 Div 1 (Explosion-Proof). IP66.

Configure

$2,389.61 
Page: 1 | 2 | All
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.