Intec Controls PolyGard SPC3-3300 Sigle-Point Gas Detector for Combustibles 0-100% LEL (Catalytic Bead), 2 relay outputs, 1 4-20mA & 2-10V analog output, 83 db horn. Wall mounted. NEMA 4X Enclosure. Accepts one additional analog remote device and a secondary gas, temperature or humidity sensor. UL Listed and CSA Certified. Available gases: Ammonia, Ethylene, Ethyl Alcohol, Ethyl Acetate, Benzene, n-Hexane, n-Heptane, Hydrogen, Isopropyl Alcohol and Methanol. *** phased out replaced by SGC6 ***

Inquiry

APPLICATION

To detect and control levels of combustible gases, vapors, and other gases in a wide variety of commercial and industrial applications such as Combustible gas level in boiler rooms (i.e. Methane), dry cell battery rooms (i.e. Hydrogen), gas/fuel spill locations (i.e. Gasoline, Hexane), laboratories and industries (i.e. Butane, Propane), etc. The controller can communicate with any compatible electronic analog control, DDC/PLC control or automation system via binary and/or analog output signal.

FEATURES
  • Continuous monitoring
  • One (1) built-in combustible catalytic bead sensor
  • Performance tested sensor to UL 2075
  • Easy plug-in sensor
  • One (1) remote analog input, 4-20 mA
  • One (1) digital input
  • Two (2) relay outputs:
    Four stage control
    Fail-safe assignable
  • One (1) analog output, (0)4-20 mA / (0)2-10 VDC - Selectable for low, high, or averaging
  • One (1) 24 VDC switched output
  • Liquid Crystal Display (LCD)
  • LED status indicators
  • Accepts toxic or combustible gas, refrigerant, temperature or humidity secondary remote sensor input
  • Built-in horn
  • Keypad user interface
  • Simple menu-driven programming
  • Modular technology
  • Overload & short-circuit protected
  • NEMA 4X enclosure
  • Easy maintenance

Specifications
Electric
Power supply 24 VAC/VDC, -20%/+15% 50/60 Hz, reverse polarity protected
Power consumption 5 VA (0.2 A) w/ (1) remote sensor connected
Sensor Performance
Gas detected Combustible gases and vapors; refer to “Ordering Information” table
Sensor element Catalytic bead (pellistor), diffusion
Range 0-100% LEL;
Accuracy & Resolution ± 1 % of reading
Repeatability ± 2 % of reading
Long term output drift < 0.5 % LEL methane /month
Response time t 90 < 10 sec. methane
Sensor life expectancy 3 yrs. normal operating environment
Sensor coverage Dependent on the target gas
Installation Location
Mounting height Dependent on the target gas
Type of Control
General Four-stage (S1 to S4) control, assignable up to two (2) binary/ relay, horn/audible alarm, and 24 VDC / 50 mA switched outputs, i.e. low-high stage for relay output, horn / audible alarm and switched 24 VDC at any stage for remote alarming
Analog input One (1) 4-20 mA, for additional remote sensor, load < 55 mA / 200 Ω, reverse polarity protected
Analog reading Current and mean (average) value
Stage level / setpoint Field adjustable over full range, four (4) stages (S1 to S4) per analog input, assignable to current or mean (average) value
- hysteresis/ switching differential Selectable for each sensor point
Digital input One (1); can be assigned to any relay (R1, R2)
- application Remote audio/visual alarm reset or override function
Type of Control (cont...)
Relay outputs (R1, R2) w/ status LEDs (1) SPDT (R1), and (1) SPST-NC or SPST-NO (R2), jumper selectable
Contact rating
-each stage level (S1-S4)
-sensor fail-safe
30 VAC/VDC, 0.5 A, max.
Assignable to any relay
Assignable to any stage level
Time delay switching Selectable for make and brake of each sensor point (SP1 to SP2) 0‐9,999 seconds
Analog output One (1), (0)4‐20 mA, load < 500 Ω;(0)2-10 VDC, load > 50K Ω; jumper selectable; polarity protected, assignable to low, high or averaging of sensor inputs
VDC switched output One (1) 24 VDC, 50 mA max
Audible alarm 83 db @ unit, enabled or disabled, selectable; assignable to stage level S1, S2, S3 or S4
Alarm acknowledgment Menu-driven and system reset function for latched relays
User Interface
Keypad type Refer to illustration “Keypad User Interface”
Touch buttons Four (4)
Status LED’s Four (4), for system on, stage status, and failure
Digital display Liquid Crystal Display (LCD), two lines, 16 characters per line, 1 digit resolution
-unit display Menu selectable, per sensor; ppm, %v/v, %LEL, °F or %RH
Environmental
Permissible ambient
-working temperature 14°F to 122°F (-10°C to 50°C)
-storage temperature 23°F to 86°F (-5°C to 30°C)
-humidity 15 to 95% RH, non-condensing
-working pressure Atmospheric ± 10%
Physical
Enclosure (panel)
-material Polycarbonate, UL 94-HB, fire-retardant
-conformity UL 50 standards
-color Light gray
-protection NEMA 4X (IP65)
-installation Wall (surface) mounted, or single gang electrical box
Dimensions (H x W x D) 5.12 x 5.12 x 2.95 in. (130 x 130 x 75 mm)
Cable entry 3 holes for 1/2 in. conduit for wall (surface) mounting and 1 hole on back side of base plate for single gang electrical box mounting
Wire connection Terminal blocks, screw type for lead wire
Wire size Min. 24 AWG (0.25 mm 2 )
Max 14 AWG (2.5 mm 2 )
Wire distance Max. loop resistance 450 Ω (= wire distance plus controller input resistance)
Weight 0.6 lb. (0.3 kg)
Approvals / Listings
-unit rating NRTL Perf Tested & Certified
Conforms to STD ANSI/UL 2075
CE
EMV-Compliance 2004/108/EWG
Low voltage directive 73/23/EWG
-relays (R1-R2) UL Recognized, E41515
CSA, C22.2 No. 0, No. 14 (File No. LR31928)
-enclosure UL Listed, E208470
CSA Certified, E208470
Warranty Two years material and workmanship, 12 months normal exposure for sensor element
Specifications
Combustible Gases/Vapors % v/v*
Ammonia (NH3) 15.0
Ethylene (C2H4) 2.3
Ethyl Alcohol (C2H5OH) 3.3
Ethyl Acetate (CH3COOC2H5) 2.2
Benzene (C6H6) 1.2
n-Hexane (C6H14) 1.1
n-Heptane (C7H16) 1.05
Hydrogen (H2) 4.0
Isopropyl Alcohol ((CH3)2CHOH) 2.2
Methanol (CH3OH) 6.7
> LEL CATALYTIC BEAD :    28 Items found.
965-525420-100
(5006)

DETCON  965-525420-100

Detcon MicroSafe FP-524D Smart gas detection Sensor designed to detect and monitor combustible gases with range 0-100% LEL using matched-pair catalytic bead sensor technology. Aluminum Junction Box. 4-20mA output. LED Display. Explosion Proof. IP66. CSA and ISA Approved for Class I, Division 1, Groups B, C, & D.

52001AL-0-9070/100P/L0
(7121)

RC SYSTEMS  52001AL-0-9070/100P/L0

RC Systems SenSmart 5200 3-wire gas detector with Catalytic Bead sensor for Hydrocarbons and Hydrogen (ammonia, butane, ethane, ethanol, hexane, hydrogen, Isopropyl alcohol, pentane, propane, propene, propylene) 0-100% LEL with GEN2 smart sensor, Color backlit LCD Display and 4-20mA output, 10-30 VDC. Aluminum or Stainless Steel enclosure. CSA Class I Division 1 (Explosion-Proof). Optional 2 RS-485 Modbus ports, 2 Programmable Alarm and Fault Relays.

Configure

$1,594.80 
XNXUTAVNNCB1
(852)

HONEYWELL  XNXUTAVNNCB1

Honeywell XNX Universal Gas Detector Transmitter including MPD CATALYTIC BEAD sensor combustible 0-100% LEL (Lower Explosive Limit) Methane (Natural Gas). Backlit LCD Display, HART® over 4-20mA output,UL/CSA approved, 5 x 3/4"NPT entries and painted Aluminum. UL Certified Class 1, Div 1 Groups A, B, C, D / ATEX Zone 1, SIL-2, INMETRO

Configure

$1,728.46 
XCDRFDL
(3004)

HONEYWELL  XCDRFDL

Honeywell Sensepoint XCD RFD (Remote Flammable Detector) Kit. Includes transmitter with LM25, 3/4“NPT Entry, 705 sensor, and 3 wire junction box. Tri-colour backit display. Outputs include 2 programmable alarm relays, 1 programmable fault relay, 4-20mAoutput (sink or source selectable). Sensor can be mounted up to 30 metres (100 feet) from transmitter. cCSAus Certified for North America. Class 1, Div 1, Groups B, C, & D.

Configure

$1,734.98 
967-521520-100
(5005)

DETCON  967-521520-100

Detcon FP-700 non-intrusive Smart Sensor designed to detect and monitor combustible gases with range 0-100% LEL using catalytic bead sensor technology. Aluminum or Stainless Steel Junction Box. 4-20mA and Modbus RS-485 outputs. LED Display. Explosion Proof. IP66. CSA, ATEX, CE and SIL2 Approved.

966-524520-100
(6100)

DETCON  966-524520-100

Detcon FP-624D Combustible 0-100% LEL Smart Sensor with catalytic bead. Includes detector in stainless steel housing, base connector board, explosion proof enclosure, splashguard, 4-20 mA output, RS-485 serial communication and 3 alarm relays. IP66. CSA approval for Class I, Division 1, Groups C & D.

32001AL-0-9071/100P/L0
(6894)

RC SYSTEMS  32001AL-0-9071/100P/L0

RC Systems SenSmart 3200 3 wire gas detector with Catalytic Bead sensor for Hydrocarbons and Hydrogen (ammonia, butane, ethane, ethanol, hexane, hydrogen, Isopropyl alcohol, pentane, propane, propene, propylene) 0-100% LEL with 'ST-48' smart transmitter. Includes Graphic LCD Display, LED indicator and 4-20mA output, optional alarm relays and Modbus RTU. 10-30 VDC. Aluminum or Stainless Steel enclosure. CSA certified for Class 1 Div 1 (Explosion Proof).

Configure

$1,967.53 
6200AL1-0-109070/100P
(7019)

RC SYSTEMS  6200AL1-0-109070/100P

RC Systems SenSmart 6200 3 wire Dual Channel Gas Detector for Hydrocarbons and Hydrogen Catalytic Bead sensor (acetylene, ammonia, butane, ethane, ethanol, hexane, hydrogen, isopropyl alcohol, methane, pentane, propane, propene or propylene) 0-100% LEL with 'ST-44' smart transmitter and GEN2 smart sensor. Includes Color TFT Display, 4-20mA output. OPTIONAL two RS-485 Modbus ports, embedded Ethernet with Webserver, Modbus TCP, 2 Alarm + Fault Relays. 10-30 VDC. Aluminum, Stainless Steel or Poly enclosure. CSA certified for Class 1 Div 1 (Explosion-Proof). IP66.

Configure

$2,389.61 
Page: 1 | 2 | All
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.