Mini-IAMs (Individual Addressable Module) provide
remote monitoring of a single input and have a small
size suitable for convenient mounting
These MX Technology addressable I/O (input/output)
modules provide flexible monitoring and control to satisfy
a variety of applications. Each is individually addressable
and communicates with an MX Loop Module located in
the host fire alarm control panel.
Features
- Small size for single input circuit monitoring of normally open or normally closed contacts
- Provides open and short circuit monitoring of the line
- Fits in small devices such as flow switches, special detection devices, and explosion proof callpoints
- A variation of this module is used in addressable callpoints and pull stations
- Dimensions are 1 ⅞” W x 2 5⁄16” H x ½” D (48 mm x 58 mm x 13 mm)
- If mounted separately from the device being monitored, select electrical box with cover plate per dimensions above
- Modules with covers mount in a standard dual gang MK box
- UL listed to Standard 864
Compatibility:
- For use with Simplex® 4100ES, 4010ES, and 4100U series fire alarm control panels equipped with an MX Loop Module
- Refer to data sheet S4100-0059 for MX Loop Module details