Det-tronics Gtxsn26n5 | Det-tronics | Transmitters | Gasdetectorsusa
Gas Leak and Flame Detectors, Analyzers, Alarm Devices and Calibration Gas

DET-TRONICS   GTXSN26N5

SKU# (7249)



DET-TRONICS GTXSN26N5
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
Det-tronics GTX Electrochemical Toxic Gas Transmitter for GT3000 Series Detectors. Two-wire loop powered. 12-30 VDC. 4-20 mAoutput signal with HART. Explosion proof. IP66. FM/CSA and IECEx approved. Suitable for Class I Div 1, Div 2 and Zone 1.
009480-323

GTXSN26N5   
Please Email us your request for quote   

Threads

   In Stock  ]

Standard configurations typically available in In Stock:
GTXSM26N5
2 Variants of base SKU
DESCRIPTION

The Det-Tronics GT3000 line of electrochemical gas detectors is designed to provide continuous monitoring of the atmosphere for potentially hazardous gas leaks or oxygen depletion. Models are available for detecting a variety of gas types in various concentration ranges.

The GT3000 toxic gas detector is a two-wire loop powered device and is designed as a stand alone unit that supports local calibration. It is also fully compatible with the FlexVu ® UD10/UD20/UD30 Universal Display Units.

The GT3000 consists of a replaceable sensor module (GTS) connected to a transmitter module (GTX). The transmitter generates a 4-20 mA output signal with HART, which is proportional to the concentration of the target gas and directly corresponds to 0-100% full scale.

The electrochemical sensor cell uses capillary diffusion barrier technology for monitoring gas concentrations in ambient air. When compared to solid state type sensors, the electrochemical sensing element provides improved accuracy, stability and reliability, and can also extend calibration intervals. This results in superior performance and reliability, as well as reduced maintenance.

HIGHLIGHTS
  • Performance approved and verified
  • Electrochemical sensor cell for increased accuracy, stability and reliability
  • Highly specific response reduces the chance of false alarms resulting from the presence of other gases
  • Self-contained transmitter circuitry
  • Temperature compensated to ensure consistent performance over entire operating temperature range
  • Suitable for outdoor applications requiring IP66 rating
  • Hydrophobic filter easily replaced without opening the device or use of tools
  • Hot swappable IS sensor module for live maintenance without de‑classification of hazardous area
  • EMI/RFI hardened
  • Event and calibration logs are stored in non-volatile memory and are accessible using a UD10/UD20/UD30, HART device or AMS software.
  • Real-time clock with battery back-up
  • Magnetic switch and LEDs for user interface

SPECIFICATIONS
Calibration Sensors are calibrated at the factory. Gas type and range are read by the transmitter. Calibration is initiated at the detector, at the UD10/ UD20 Universal Display Unit, or by some other HART interface device. Calibration cannot be initiated from the UD30.
Operating Voltage 24 Vdc nominal; Operating range is 12 to 30 Vdc
Power Consumption 0.8 watt maximum @ 30 Vdc
Max. Loop Resistance 300 ohms at 18 Vdc, 600 ohms at 24 Vdc
Current Output 4-20 mA (Normal operating mode)
3.8 mA indicates calibrate mode
3.5 mA or less indicates a fault condition
Wiring 2x22 AWG, 1x16 AWG, 600V, 20"
Storage Temp. (GTX) –55°C to +75°C (–67°F to +167°F)
(GTS) 0°C to +20°C (+32°F to +68°F) Ideal: +4°C to +10°C (+39°F to +50°F)
Storage Life 6 months in factory-sealed packaging
Humidity Range 15 to 90% RH.
Tropicalization / PC BD Protection Conformal coated printed circuit boards: CTI Rating of 600V, maximum allowed by standard Third party tested per ASTM-D-3638-07
Pressure Range Atmospheric ±10%
Warm-Up Warm-up time can last up to 150 seconds
Thread Options 3/4" NPT or M25
Enclosure Material GTX Transmitter: 316 Stainless Steel
GTS Sensor Module: PPA (30% Carbon filled)
Expected Operating Life GTS: 2 years in an open air environment
Expected Shelf Life GTS: 6 months in factory sealed packaging
Warranty (For the GTX. See Table below for the GTS) 18 months from date of shipment
Certification (Explosion-Proof Model) FM: Class I, Div. 1, Groups A, B, C & D
Class I, Zone 1, Group IIC
IP66
Conduit seal not required
Acidic atmospheres excluded
CSA:
Class I, Div. 1, Groups A, B, C & D (T6)
Class I, Div. 2, Groups A, B, C & D (T6)
IP66
IECEx:
Ex d mb [ia Ga] IIC T4 Gb IP66
IECEx FMG 10.0003X
UL-BR 15.0752X
Ex db mb [ia Ga] IIC T4 Gb IP66
Tamb –40°C to +50°C (H 2 S)
Tamb –20°C to +50°C (other)
Certification (Intrinsically Safe Model) FM: IS Class I, Div. 1, Groups A, B, C & D
Class I, Zone 0, Group IIC
Performance verified per ANSI/ISA
92.00.01 and FM6340
IP66
CSA: Class I, Div. 1, Groups A, B, C & D (T4)
IP66
IECEx:
Ex ia IIC T4 Ga IP66
IECEx FMG 08.0005X
INMETRO:
UL-BR 15.0404X
Ex ia IIC T4 Gb IP66
Tamb –40°C to +50°C
Certification (SIL Approval) IEC 61508
Certified SIL 2 Capable
SIL Certification includes H 2 S, H 2 S+ and O 2 models only
Export Info
Harmonized Tariff Code (HTC)9027102000

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer/Electronic Payment and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> DET-TRONICS :    26 Items found.
010569-001
(7247)

DET-TRONICS  010569-001

Det-tronics 010569-001 UD10 Display Module. Relay / 4-20 mA Output.



 
(7434)

DET-TRONICS  012287-002

Det-tronics 012287-002 LS2000 Alignment Tool



 
UD10S5N28W2
(7262)

DET-TRONICS  UD10S5N28W2

Det-tronics FlexVu UD10 Explosion-Proof Universal LCD Backlit Display Unit. 24 VDC. Includes 4–20 mA output with HART, relay contacts, and Modbus RS485. Eventm fault and alarm logs. FM, CSA, ATEX, IECEx and SIL 2 certified for Class I Div 1 and Div 2, Zone 1 and Zone 2.

010970-004
(7248)

DET-TRONICS  010970-004

Det-tronics 010970-004 UPGRADE KIT UD10S5N25T2. Allows field conversion of a Digital Communication Unit (DCU) to a FlexVu UD10 Universal Display. Adds relay, 4-20 mA, RS485 and HART outputs. FM, CSA, ATEX, IECEx and SIL 2 Approvals.



 
009174-013
(7430)

DET-TRONICS  009174-013

Det-tronics 009174-013 EQ3730 8 Channel Enhanced Discrete Input/Output Module (EDIO) with DIN Rail mounting. FM, CSA, ATEX, IECEx and SIL 2 approvals.



 
EQ3001PCSW-C
(7433)

DET-TRONICS  EQ3001PCSW-C

Det-tronics EQ3001 Eagle Quantum Premier Controller for up to 246 Nodes. Includes 3 RS-232, 2 RS-485 ports and 8 Programmable Relay Outputs. Modbus RTU, Modbus TCP/IP or Allen Bradley protocols. FM, IEC, SIL 2 approvals.



 
Page: 1 | 2 | All
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.