Notifier H365 | Intelligent | Thermal | Gasdetectorsusa
Gas Leak and Flame Detectors, Analyzers, Alarm Devices and Calibration Gas

NOTIFIER   H365

SKU# (7239)
NOTIFIER H365
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
Notifier H365 Addressable Intelligent Heat Detector. Two-wire SLC loop connection. Fire-resistant plastic enclosure. 15-32 VDC. UL, FM and CSFM listed.

UL   FM

Please Email us your request for quote   

   4 Weeks  ]

The Fire•Lite® Alarms H365(A), H365R(A), and H365HT(A) addressable plug-in thermal detectors are designed for both performance and aesthetics and are a direct replacement for the H355 Series. A new modern, sleek, contemporary design and advanced thermal technologies make the H365(A) Series ideal for both system operation and building design.

Exclusively for use with Fire•Lite’s addressable fire alarm control panels, the H365(A) Series point ID capability allows each detector’s address to be set with rotary, decimal address switches, providing exact detector location for emergency personnel to quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication.

The H365(A) Series includes fixed temperature, rate-of-rise and high heat fixed temperature detectors that provide effective, intelligent property protection for a variety of applications. Detectors are available for both LiteSpeed™ and CLIP applications as designated.

Features SLC LOOP:
  • Two-wire SLC loop connection
  • Unit uses base for wiring
ADDRESSING:
  • Addressable by device
  • Rotary, decimal addressing (Refer to the Fire•Lite panel manuals for device capacity.)
ARCHITECTURE:
  • Designed to meet UL 268 7th Edition
  • Sleek, low-profile, stylish design
  • State-of-the-art thermistor technology for fast response
  • Integral communications and built-in device-type identification
  • Built-in tamper resistant feature
  • Built-in functional test switch activated by external magnet
OPERATION:
  • Fixed temperature model (H365(A)) factory preset to 135°F (57°C)
  • Rate-of-rise model (H365R(A)), 15°F (8.3°C) per minute
  • High-temperature model (H365HT(A) ) factory preset to 190°F (88°C)
  • 360°-field viewing angle of the two visual alarm indicators, LEDs blink red in Normal condition and turn on steady red in Alarm
  • LEDs blink every time the unit is polled
MECHANICALS:
    Sealed against back pressure SEMS screws for wiring of the separate base Designed for direct-surface or electrical-box mounting Plugs into separate base for ease of installation and maintenance Separate base allows interchange of photoelectric, ionization and thermal sensors
OTHER SYSTEM FEATURES:
  • Remote test feature from the panel
  • Walk test with address display
  • Low standby current
OPTIONS:
  • Remote LED output connection to optional RA100Z remote LED annunciator
Installation

H365 Series plug-in intelligent thermal detectors use a detachable base to simplify installation, service and maintenance. Installation instructions are shipped with each detector.

Mount detector base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DF-60059.

NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring only. When using relay or sounder bases, consult the I300(A) installation sheet I56-3626 for device limitations between isolator modules and isolator bases.

Applications

Use thermal detectors for protection of property. For further information, refer to I56-6525, Applications Manual for System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications.

Construction

These detectors are constructed of fire-resistant plastic. The H365 Series plug-in intelligent thermal detectors are designed to commercial standards and offer an attractive appearance.

Operation

Each H365 Series detector uses one of the panel’s addresses (total limit is panel dependent) on the Fire•LiteJCI Signaling Line Circuit (SLC). It responds to regular polls from the control panel and reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The H365 Series offers features and performance that represent the latest in thermal detector technology.

Listings and Approvals

Listings and approvals below apply to the H365 Series detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL/ULC Listing: S2517
  • FM Approved
  • CSFM: 7272-0075:0501

SYSTEM SPECIFICATIONS
Size:2.0" (5.3 cm) high; base determines diameter
– B300-6: 6.1" (15.6 cm) diameter
– B501: 4" (10.2 cm) diameter
For a complete list of detector bases see DF-60983
Shipping weight:3.4 oz. (95 g)
Operating temperature range:• H365, H365R Series: –4°F to 100°F (–20°C to 38°C)
• H365H Series: –4°F to 150°F (–20°C to 66°C)
Detector spacing:UL approved for 50 ft. (15.24 m) center-to-center, FM approved for 25 x 25 ft. (7.62 x 7.62 m) spacing
Relative humidity:10% – 93% non-condensing
Thermal ratings:fixed-temperature set point 135 ° F (57°C), rate-of-rise detection 15°F (8.3°C) per minute, high temperature heat 190°F (88°C)
Mounting:B300-6(A) flanged base, included
ELECTRICAL SPECIFICATIONS
Voltage range:15 - 32 volts DC peak
Standby current (max. avg.):200µA @ 24 VDC (one communica- tion every 5 seconds with LED enabled)
Max current:4.5 mA @ 24 VDC (“ON”)
Export Info
Made inMexico
Harmonized Tariff Code (HTC)85311001

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer/Electronic Payment and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> INTELLIGENT :    24 Items found.
FCO-951
(3502)

NOTIFIER  FCO-951

Notifier IntelliQuad PLUS FCO-951 Advanced Multi-Criteria Fire/CO Detector with four unique sensing elements: Carbon Monoxide (CO) electrochemical sensor, Infrared (IR) sensing measure, Photo-electric smoke detection and Thermal detection. UL listed. *** replaces FSC-851 ***



 
FSV-951R
(3229)

NOTIFIER  FSV-951R

Notifier FSV-951R Series Very Intelligent Plug-in Early Warning (VIEW) Laser Smoke Detector. 0.03% to 1.00% (CLIP) or 0.02% to 2.00% (other) sensivity. With FlashScan and CLIP protocol systems. Advanced laser light source and 360° viewing angle. Optional relay, isolator and sounder bases. UL and MEA listed. FM, CSFM, BSMI and CCCF Approved. (replaces FSL-751)

4098-9756
(7075)

SIMPLEX TYCO  4098-9756

Simplex Tyco 4098-9756 Addressable Duct Sensor Housing with TrueAlarm Photoelectric Smoke Sensor. Includes relay, supervised output for multiple remote relays and 2 diagnostic LEDs. IDNet and MAPNET II communications. UL listed (requires separate 24 VDC fire alarm power).



 
FS-OSI-RI
(6933)

NOTIFIER  FS-OSI-RI

Notifier FS-OSI-RI Intelligent Addressable Single-ended Reflective Imaging Beam Smoke Detector suited for large open areas with high ceilings. 24 VDC. 12° field of view. Status LED indicators. UL and FM approved.



 
Page: 1 | 2 | All