SPECIFICATIONS: FSL100 SERIES FLAME DETECTORS |
FSL100 Flame Detector types | FSL100-UV, FSL100-UVIR and FSL100-IR3; Choice of red or white housings |
Range | 110 ft /35 m (IR3), 25 m/80 ft (UV, UV/IR) alarming within 10 seconds to a 1 ft2(0.1 m 2 )n-heptane fire |
Cone of vision | 90 ̊minimum horizontal and vertical |
Power | 10-28 VDC (12-24 VDC nominal) |
Local LEDs | Continuous green: normal operation
Continuous yellow: fault
Flashing yellow: Fault and guide to repeat self-test after a self-test failure
Continuous red: alarm |
Current output | Standard available 4–20 mA (stepped, sinking, non-isolated)
0 mA power fault / microprocessor fault
2 mA optical fault
4 mA normal operation
>20 mA alarm |
Relay output:
- Alarm relay
- Fault relay | De-energized during normal operation, no alarm, SPDT, 30 VDC – 2 A, 60 W max. Energised during normal operation, no fault,
SPDT, 30 VDC – 2 A, 60 W max |
Cable gland & terminals | Cable entry M20 clearance. Supplied with gland suitable for cable diameter from 0.2” (5.5mm) to 0.5”(13mm). Terminals suitable for 0.5mm 2 (20AWG) to 1.5mm 2 (15AWG) wire |
Start up times | <10 sec |
Alarm response time | 8 to 30 sec |
Alarm output settings | Selectable LEDs and relays latching/non-latching; factory setting: latching |
Automatic & manual Self-Test | Automatic Sensor Test (built in Self-Test) and manual Self-Test |
Operating current normal | 25 mA at 24 VDC |
Current in alarm, at 24 VDC | ±75 mA at 24 VDC |
Connections to: | Fire control panels using end of line (EOL) and alarm resistors (current increase)
Devices that operate via relay switched outputs
PLCs with 4–20 mA inputs |
End of line and alarm resistor | To be adjusted to the fire control panel; free terminals are dedicated to the resistors
Note: the alarm and EOL resistor must be rated 2 W min. each and the total power dissipation of both alarm and EOL resistor should not exceed 2 W |
Housing | Glass Reinforced Polyester (GRP), Non-incendive. UV resistant, Self-Extinguishing V–0 (UL-94) |
Swivel Mount | PA66, UV resistant; Stainless Steel fixings; 280 g (0.62 lb) |
Pressure compensating element | PCE (Pressure Compensating Element) avoids moisture build-up in the detector housing due to changes in ambient air-pressure |
Dimensions | 4.9 x 3.15 x 2.25 in (125 x 80 x 57 mm) |
Weight | 1.05 lb (465 g) |
Ingress protection | IP65 |
Temperature, operating | –40 ̊F to +158 ̊F (–40 ̊C to +70 ̊C) |
Temperature, ambient ATEX and FM class 3611 | –13 ̊F to +158 ̊F (–25 ̊C to +70 ̊C) |