Honeywell Fire Sentry FS10-R Unitized Infrared Fire Detector for Automatic Electrostatic Paint Spray Booths. Multi-spectral and electro-optical. Includes RS-485 interface and 3 relays. Explosion Proof. 24VDC power input. NFPA 33 Standard. FM and CE Approved.

FS10-R30   
2,855.51

Alert type
Sensivity
Housing
Grill Kit
Kit includes: (1) SS grill, (2) SS brackets, and (2) SS screws
Mounting Assembly

   12 Weeks  ]
4 Variants of base SKU

Our fire detection systems have been protecting electrostatic paint spray booths worldwide – with millions of booth operational hours and not a single fire loss.

Features
  • Multi-Spectral digital electro-optical infrared fire detector
  • Meets requirements of NFPA 33
  • Unique two-stage ALERT and FIRE ALARM response
  • Immune to false alarms caused by arcs or corona discharges
  • Built-in automatic “through the lens” self-test
  • Not sensitive to background radiant energy sources such as paint heaters
  • Not affected by absorbing smoke or paint solvent mist in liquid pant spray booths
  • Sees through paint, powder or oil residue on detector’s lens
  • Digital communications with RS-485 interface
  • FirePicTM: retrieval of recorded pre-fire data
  • SnapShotTM: dynamic graphical display of what the detector sees
Applications (indoor use only)
  • Liquid Paint Spray Lines
  • Aerosol Filling
  • Powder Coating Booths
  • Curing Ovens

The Fire Sentry FS10-R Unitized is a multi-spectral infrared electro-optical flame detector designed specifically for liquid paint or powder spray booth applications. Based on the Fire Sentry FS System 10, the FS10-R Unitized flame detector meets the need for a stand-alone capability and complies with the NFPA 33 Standard. The WideBand IRTM, NearBand IR, and Visible sensors combined with the advanced signal procession provide optimum performance. High spend fire response with optional factory sensitivity settings and alarm outputs provide the best, proven solution to fire detection for the Finishing Industry.

Operation

The Fire Sentry FS10-R Unitized detector is designed to operate with any approved fire alarm panel. Interface with fire alarm panel is accomplished using the detector’s ALARM, ALERT and FAULT relays.

When power is applied, a self-test is automatically performed and the FAULT relay is energized to show that the detector has no faults. The front LED blinks every ten seconds to indicate normal operation.

In normal operation, the continuous spectral data stream of information from the sensor array is analyzed by the microprocessor. With two distinct relay outputs, the Fire Sentry FS10-R Unitized provides an ALERT output for spray gun “fireball” type fires, and if the fire continues a FIRE ALARM is declared in 4-5 seconds.

The detector stores all the pre-fire spectral data from the sensor array in non-volatile memory for retrieval and evaluation. The Fire Sentry FS10-R stores the last six FirePicTM events, each 8 seconds long; and 200 event histories with time and date stamp. The FirePic data can then be used to postulate the cause of the fire.

GENERAL SPECIFICATION
Sensitivity 45 ft. and 30 ft. to a 1 sq. ft. gasoline fire*
Response time Alert: 0.3 second (response to “fireball” type fires)
Fire Early Warning: 1 second (early response to a fire alarm)
Fire Alarm: Less than 5 seconds (if fire continues)
Field of View 90° (± 45° horizontal and vertical)
Spectral Sensitivity Visible: 400 – 700 nanometers
Near Band IR: 0.7 – 1.1 microns
Wide Band IR: 0.7 – 3.5 microns
Input power 24 VDC nominal (18-32 VDC) - Regulated
Power consumption Normal: 85 mA (typical); Alarm: 120 mA (typical)
Output Relays Alert/Early Warning: SPST, N.O.*
Fire Alarm: SPST, N.O.
Fault: SPST, N.O. with no power
Contact ratings: 1 amp @ 24 VDC
Normal operation Fault relay is Energized, Non-Latching
All other relays are De-energized
Fire and Alert relays are available
Latching or Non-Latching
Operating temperature Operating: -40o to +185oF (-40o to +85oC)
Humidity Range 10% to 90% relative humidity, non-condensing
Weight Aluminum: 3.8 lbs (1.7 kg)
Enclosure Copper-Free Powder Coated Aluminum or optional 316 Stainless Steel; NEMA 3, 4 and 4X
Conduit entries Two 3⁄4” NPT
Certifications Explosion-Proof; Class I, Div. 1 & 2, Groups B, C, & D
Class II, Div. 1 & 2, Groups E, F, & G
Class III
FM, CE
Dimensions 4.81 in. diameter; 4.65 in. deep
Mounting Swivel Bracket Assembly - Optional
Warranty Two years from date of shipping
Export Info
Made inUnited States
Harmonized Tariff Code (HTC)90318099

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> ACCESSORIES - RELATED - CONSUMABLES :    1 Items found.
FT-S7
(4599)

HONEYWELL  FT-S7

Honeywell IR test lamp, battery operated for testing FS7/FS10 Fire Detectors up to 2 ft. distance



$994.17 
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.