NOTIFIER   XP10-M

SKU# (3724)
NOTIFIER XP10-M
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
Notifier XP10-M Ten Input Monitor Module for intelligent alarm systems. Up to 10 addresable Class B or 5 addressable Class A devices. SLC inputs. Green LED indicators. Flexible mounting options. FlashScan or CLIP operation. UL Listed. CSFM, FM, MEA and MSTM approved.

Please Email us your request for quote   

   4 Weeks  ]

The XP10-M ten-input monitor module is an interface between a control panel and normally open contact devices in intelligent alarm systems such as pull stations, security contacts, or flow switches.

The first address on the XP10-M is set from 01 to 150 and the remaining modules are automatically assigned to the next nine higher addresses. Provisions are included for dis- abling a maximum of two unused addresses.

The supervised state (normal, open, or short) of the moni- tored device is sent back to the panel. A common SLC input is used for all modules, and the initiating device loops share a common supervisory supply and ground — otherwise each monitor operates independently from the others.

Each XP10-M module has panel-controlled green LED indi- cators. The panel can cause the LEDs to blink, latch on, or latch off.

NOTE: Unless otherwise specified, the term XP10-M is used in this data sheet to refer to both the XP10-M and the XP10-MA (ULC-listed version) .

FEATURES

  • Listed to UL Standard 864, 9th edition.
  • Ten addressable Class B or five addressable Class A initi- ating device circuits.
  • Removable 12 AWG (3.31 mm2) to 18 AWG (0.821 mm2) plug-in terminal blocks.
  • Status indicators for each point.
  • Unused addresses may be disabled.
  • Rotary address switches.
  • Class A or Class B operation.
  • FlashScan® or CLIP operation.
  • Flexible mounting options.
  • Mounting hardware included.
Agency Listings and Approvals

The listings and approvals below apply to the XP10-M(A) Ten- Input Monitor Module. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL Listed: S635
  • CSFM approved: 7300-0028:219
  • FM approved
  • ULC Listed: S635 (XP10-MA)
  • MEA approved: 43-02-E
  • Maryland State Fire Marshal approved: Permit #2106

XP10-M(A) SPECIFICATIONS
Standby current: 3.5 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases).
Alarm current: 55 mA (assumes all ten LEDs solid ON).
Temperature range: 32°F to 120°F (0°C to 49°C) for UL applications; –10°C to +55°C for EN54 applications.
Humidity: 10% to 85% noncondensing for UL applications;
10% to 93% noncondensing for EN54 applications.
Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm) wide x 1.25" (31.75 mm) deep.
Shipping weight: 0.76 lb. (0.345 kg) including packaging.
Mounting options: CHS-6 chassis: Up to 6 modules.
BB-25 cabinet: Up to 6 modules.
BB-XP cabinet: One or two modules.
CAB-4 Series cabinet: See DN-6857.
EQ Cabinet Series: See DN-60229.
Wire gauge: 12 AWG (3.31 mm2) to 18 AWG (0.821 mm2).
Power-limited circuits must employ type FPL, FPLR, or FPLP cable as required by Article 760 of the NEC.
XP10-M is shipped in Class B position; remove shunt for Class A operation.
Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent.
Maximum IDC wiring resistance: 1500 ohms.
Maximum IDC voltage: 10.2 VDC.
Maximum IDC current: 240 μA.
Export Info
Made inMexico

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer/Electronic Payment and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> NOTIFIER :    42 Items found.
HS-NCM-MF__
(4326)

NOTIFIER  HS-NCM-MF

Notifier HS-NCM High-Speed Network Communications Module. Single or Multi-mode versions available. Allow connection from Notifier Panels to NOTI•FIRE•NET with a fiber-optic cable or twisted-pair wire. NFPA Style 4 (Class B) or Style 7 (Class A) operation. 24 VDC, 100Mb baud transmission rate. UL, ULC, CSFM and FM approved.

CPU2-3030D
(6931)

NOTIFIER  CPU2-3030D

Notifier CPU2-3030D Central processing unit for an NFS2-3030 system. Keypad/display installed; includes 640-character backlit LCD display, QWERTY programming and control keypad. Requires an AMPS-24(E) power supply.

Page: 1 | 2 | 3 | All
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.