NOTIFIER’s XP6-C six-circuit supervised control module
provides intelligent alarm systems with supervised monitoring
of wiring to load devices that require an external power supply
to operate, such as horns, strobes, or bells. Each module is
intended for switching applications involving AC DC or audio,
which require wiring supervision. Upon command from the
control panel, the XP6-C will disconnect the supervision and
connect the external power supply across the load device.
The first module is addressed from 01 to 154 while the remain-
ing modules are automatically assigned to the next five higher
addresses. Each XP6-C module has terminals for connection
to an external supply circuit for powering devices on its notifi-
cation appliance circuit (NAC). One or multiple power supplies
or amplifiers may be used.
NOTE: Provisions are included for disabling a maximum of three
unused addresses.
Each XP6-C module features a short-circuit-protection monitor
to protect the external power supply against short-circuit con-
ditions on the NAC. When an alarm condition occurs, the relay
which connects the external supply to the NAC will not be
allowed to close if a short-circuit condition currently exists on
the NAC. Additionally, an algorithm is incorporated to find
shorts when the module is active. The XP6-C module will
close all circuits that are not shorted to find the NAC with the
problem.
Each XP6-C module has panel-controlled green LED indica-
tors. The panel can cause the LEDs to blink, latch on, or latch
off.
The SYNC-1 accessory card provides the XP6-C with
additional functionality with compatible System Sensor®
SpectrAlert® and SpectrAlert Advance® audio/visual devices.
Features
- Six addressable Style B (Class B) or three addressable
Style D (Class A) outputs that function as notification appli-
ance/speaker/telephone circuits.
- Removable 12 AWG (3.31 mm2) to 18 AWG (0.821 mm2)
plug-in terminal blocks.
- Status indicators for each point.
- Unused addresses may be disabled (up to 3).
- Rotary address switches.
- FlashScan® or CLIP operation.
- Optional SYNC-1 accessory card for SpectrAlert and
SpectrAlert Advance devices.
- Mount one or two modules in a BB-XP cabinet (optional).
- Mount up to six modules on a CHS-6 chassis in a CAB-3
Series, CAB-4 Series, EQ Series, or BB-25 cabinet
(optional).
- Mounting hardware included
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
- UL Listed: S635 (XP6-C); S3705 (SYNC-1).
- ULC Listed: S635 (XP6-CA).
- MEA Listed: 43-02-E / 226-03-E (SYNC-1).
- FDNY: COA#6121.
- FM Approved (Local Protective Signaling).
- CSFM: 7300-0028:0219 (XP6-C). 7300-1653:0160 (SYNC-1).
- Maryland State Fire Marshal: Permit # 2106 (XP6-C).