The VESDA-E VES is similar to the flagship VESDA-E VEP aspirating smoke
detector but also includes a valve mechanism in the inlet manifold and software to
control the airflow from the four Sectors (pipes). This configuration enables a single
zone to be divided into four separate sectors, for example, distinguishing between
separate aisles within a data room. The VES enables the user to locate the source
of smoke by identifying the first sector to reach the Alert level. The detector then
continues to sample from all sectors to monitor fire growth and will report separate
alarm levels for each sector. The VES provides four individually configurable alarm
levels (Alert, Action, Fire 1 and Fire 2) for each sector allowing optimum protection
in a wide range of applications. Built on the Flair detection technology and years of
application experience, VES detectors achieve consistent performance over their
lifetime via absolute calibration. In addition, the VES delivers a range of revolutionary features that provide user value.
How it Works
The VES draws air from all sectors in use. If the smoke level reaches the Adaptive Scan Threshold, the VES quickly scans each sector to
identify which sector is carrying smoke. The first sector to reach the Alert level is designated as the First Alarm Sector (FAS) and this sector
is signalled to the user. If two or more sectors reach the Alert level then, the sector with the highest smoke concentration is designated as the
First Alarm Sector (FAS). Once Fast Scan is completed and the FAS identified, the VES continues to closely monitor all four sectors to track
fire growth and maintain full protection of the area.
Flair Detection Technology
Flair is the revolutionary detection chamber that forms the core of the VESDA-E VES, providing higher stability and increased longevity. Direct
imaging of the sampled particles using a CMOS imager combined with multiple photo-diodes allows better detection and fewer nuisance
alarms.
The VES Display
The VES display Home page has a bar graph to indicate the smoke level and adaptive scan threshold. Fault icons are also included to
indicate various fault conditions. When the adaptive scan threshold is exceeded the VES display automatically transitions to the Sector
status page to indicate the smoke level and alarm level per sector. If alarms are configured as latched then alarm indication per sector will be
retained until Reset is applied. The VES display can only return to the Home page under user control.
Installation, Commissioning and Operation
VESDA-E VES is equipped with a powerful aspirator that enables the use of 560 m (1,837 ft) of total pipe length. Out of box operation is
made possible with AutoConfig which allows airflow normalisation and AutoLearn Smoke and Flow to be initiated from within the detector.
VES is fully supported by Xtralis VSC and ASPIRE software applications which facilitate ease of pipe network design, system commissioning
and maintenance.
VESDAnet™
VESDA devices communicate on VESDAnet which provides a robust bidirectional communication network allowing continued redundant
operation even during single point wiring failures. VESDAnet enables primary reporting, centralized configuration, control, maintenance and
monitoring.
Ethernet connectivity
VESDA-E detectors offer connectivity to corporate networks via Ethernet, allowing for devices installed with Xtralis
monitoring and configuration software to connect to the detector.
Backward Compatibility
VESDA-E VES is compatible with existing VESDA installations. The detector occupies the same mounting footprint, pipe, conduit and
electrical connector positioning as VESDA VLS. VES is also compatible with existing VESDAnet installations allowing monitoring of both
VESDA-E and legacy detectors via the latest VSC and VSM4 applications.
Features
- Sector addressability for up to four sectors
- Adaptive scan threshold
- Flair detection technology delivers reliable very early warning in a wide range of environments with minimal nuisance alarms
- Short wavelength laser-based detection:
- High sensitivity from small particle light scattering
- No drift compensation required since focused light directed at target gives low backgrounds
- High stability with temperature and time
- Multi stage filtration and optical protection with clean air barriers ensures lifetime detection performance
- Four configurable alarm levels per sector and a wide sensitivity range deliver optimum protection for the widest range of applications
- Intuitive LCD display provides instant status information for immediate response
- Flow fault thresholds per port accommodate varying airflow conditions
- Smart on-board filter retains dust count and remaining filter life for predictable maintenance
- Extensive event log (20,000 events) for event analysis and system diagnostics
- AutoLearn™ smoke and flow for reliable and rapid commissioning
- Backward compatible with VLS and VESDAnet
- Ethernet for connectivity with Xtralis software for configuration, secondary monitoring and maintenance
- USB for PC configuration, and firmware upgrade using a memory stick
- Two programmable GPIs (1 monitored) for flexible remote control
- Field replaceable sub-assemblies enable faster service and maximum uptime
Listings / Approvals
- CSFM
- FM
- ActivFire
- VdS
- NF-SSI (www.marque-nf.com)
- CE
- UKCA
- ActivFire
- CCC
- EN 54-20, ISO 7240-20
-
-Class A (40 holes / Fire 1 = 0.067% obs/m)
-Class B (80 holes / Fire 1 = 0.085% obs/m)
-Class C (100 holes / Fire 1 = 0.251% obs/m)