The flameproof BExCS110-L2-R combination omni-directional alarm horn
sounder and high output LED beacon is suitable for Zone 1, 2, 21 & 22
applications. Approved to IECEx and ATEX standards.
The unique radial horn on the compact BExCS110-L2-R distributes the audible warning signal
omni-directionally allowing the visual signal to be orientated optimally. Sound level ouputs are up
to 115dB(A) at 1 metre with a choice of 32 alarm tones and 3 remotely selectable stages. The
LED beacon contains an array of 4 high output, multi-function L.E.D.s. with a total of 7 modes of
operation – 5 flashing modes and 2 steady modes for use in indicator / status applications. DC
voltage versions feature three remotely selectable stages enabling multiple warnings to be
signalled from one device.
Features:
- Marine grade, corrosion proof, LM6 aluminium enclosure
- Omni-directional sound output.
- Automatic synchronisation on multi-beacon & sounder systems.
- Beacons can be set to ‘flip-flop’ alternating mode with other units on multi-beacon systems.
- Very large termination area.
- Dual M20 cable entries – adaptors available.
- Stopping plug included.
- Ratchet adjustable stainless steel ‘U’ bracket.
- Reverse polarity diode fitted.
- IP66/67 ingress protection.
- 160 candela effective light intensity.
- UV stable PC, field replaceable, colour lens filters.
- ‘Stage Programmable’ version available with 45 tones & 4 remotely selectable stages.
Approvals:
- IECEx KEM 10.0025X
- ATEX KEMA 01ATEX2223X
- TR-CU Ex EAC certificate: RU C-GB.AA71.B.00109
Coding
- II 2G Ex d IIB T5 Gb Ta. -50°C to +50°C
- II 2G Ex d IIB T4 Gb Ta. -50°C to +70°C
- II 2D Ex tb IIIC T70°C Db Ta. -50°C to +40°C
- II 2D Ex tb IIIC T85°C Db Ta. -50°C to +55°C
- II 2D Ex tb IIIC T100°C Db Ta. -50°C to +70°C
Stage 1 |
WAV file |
Frequency Description. |
Stg 2 |
Stg 3 |
T 1 |
 |
Continuous 1000Hz Toxic Gas Alarm |
T 31 |
T 11 |
T 2 |
 |
Alternating 800/1000Hz at 0.25s intervals |
T 17 |
T 5 |
T 3 |
 |
Slow Whoop 500/1200Hz at 0.3Hz with 0.5s gap repeated |
T 2 |
T 5 |
T 4 |
 |
Sweeping 800/1000 at 1Hz |
T 6 |
T 5 |
T 5 |
 |
Continuous at 2400Hz |
T 3 |
T 27 |
T 6 |
 |
Sweeping 2400/2900Hz at 7Hz |
T 7 |
T 5 |
T 7 |
 |
Sweeping 2400/2900Hz at 1Hz |
T 10 |
T 5 |
T 8 |
 |
Siren 500/1200/500Hz at 0.3Hz |
T 2 |
T 5 |
T 9 |
 |
Sawtooth 1200/500Hz at 1Hz |
T 15 |
T 2 |
T 10 |
 |
Alternating 2400/2900Hz at 2Hz |
T 7 |
T 5 |
T 11 |
 |
Intermittent 1000Hz at 0.5Hz General alarm |
T 31 |
T 1 |
T 12 |
 |
Alternating 800/1000Hz at 0.875Hz |
T 4 |
T 5 |
T 13 |
 |
Intermittent 2400Hz at 1Hz |
T 15 |
T 5 |
T 14 |
 |
Intermittent 800Hz 0.25s on 1s off |
T 4 |
T 5 |
T 15 |
 |
Continuous at 800Hz |
T 2 |
T 5 |
T 16 |
 |
Intermittent 660Hz 150mS on, 150mS off |
T 18 |
T 5 |
T 17 |
 |
Alternating 544Hz (100mS)/440Hz(400mS) |
T 2 |
T 27 |
T 18 |
 |
Intermittent 660Hz 1.8s on, 1.8s off |
T 2 |
T 5 |
T 19 |
 |
1400Hz to 1600Hz sweep up over 1s -1600Hz to 1400Hz sweep down over 0.5s |
T 2 |
T 5 |
T 20 |
 |
Continuous 660Hz |
T 2 |
T 5 |
T 21 |
 |
Alternating 554/440Hz at 1Hz |
T 2 |
T 5 |
T 22 |
 |
Intermittent 554Hz at 0.875Hz |
T 2 |
T 5 |
T 23 |
 |
800Hz pulsing at 2Hz |
T 6 |
T 5 |
T 24 |
 |
Sweeping 800/1000Hz at 50Hz |
T 29 |
T 5 |
T 25 |
 |
Sweeping 2400/2900Hz at 50Hz |
T 29 |
T 5 |
T 26 |
 |
Simulated bell sound |
T 2 |
T 1 |
T 27 |
 |
Continuous 554Hz |
T 26 |
T 5 |
T 28 |
 |
Continuous 440Hz |
T 2 |
T 5 |
T 29 |
 |
Sweeping 800/1000Hz at 7Hz |
T 7 |
T 5 |
T 30 |
 |
420Hz repeating 0.625s on, 0.625s off Australian alert signal |
T 32 |
T 5 |
T 31 |
 |
1200/500Hz at 1 Hz Prepare to Abandon Platform |
T 11 |
T 1 |
T 32 |
 |
Sweeping 500/1200Hz 3.75s on, 0.25s off 15Hz |
T 26 |
T 1 |
Country specific or custom tone configurations and alarm frequencies are available upon request. |