Notifier Pse-6 | Notifier | Power Supplies | Gasdetectorsusa
Gas Leak and Flame Detectors, Analyzers, Alarm Devices and Calibration Gas

NOTIFIER   PSE-6

SKU# (6924)



NOTIFIER PSE-6
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
Notifier PSE-6 (6 amp) or PSE-10 (10 amp) 24 VDC Remote Power Supply Expander with battery charger for 12 or 24 volt alarm control panels (FACP). Up to 7 outputs. UL, ULC, CSFM and FM listed.

PSE-6   
Please Email us your request for quote   

Model

 4 Weeks  ]
6 Variants of base SKU

The PS Series is a remote power supply line from NOTIFIER and is a direct replacement for the FCPS-24S6/8 Series. The PSE-6(C)(E) is a 6 amp and the PSE-10(C)(E) is a 10 amp, remote power supply with battery charger that may be connected to any 12 or 24 volt fire alarm control panel (FACP) or used as a standalone power supply. The PS Series provides 24 VDC power for NACs (notification appli- ance circuits) configured as either Class B or Class A (requires the ZNAC-PS option card) with multiple sync protocol options. The PS Series also provides auxiliary power, constant or resettable, suited for detectors, annunciators, door holders, and other fire alarm sys- tem peripherals. The PS Series cabinet can hold two 7 AH or 18 AH batteries and can charge up to 33 AH batteries in a separate cabi- net. The PSE-6E and PSE-10E are models rated for 240V opera- tion.

Features
  • Up to five (6 amp model) or seven (10 amp model) independently-configurable, power-limited output circuits for:
    • Class B and/or Class A NACs
    • Class B and/or Class A resettable or non-resettable 24V auxiliary power
    • door holder power
  • Converts from Class B to Class A wiring without losing any outputs using the ZNAC-PS converter card (sold separately)
  • Optimal for powering four-wire smoke detectors, annunciators, and other system peripherals requiring regulated power
  • Configurable for ANSI® Temporal 3 or Temporal 4 coded output
  • UL-Listed NAC synchronization using System Sensor®, Wheelock®, Gentex®, or AMSECO® appliances
  • Synchronization can be triggered from FACP NAC/remote sync outputs, cascaded power supply, or a control module, single or multi, which may be housed within the power supply cabinet
  • Ability to cascade up to four power supplies
  • Two (6 amp model) or three (10 amp model) fully-isolated input/control circuits which can be programmed to any output
  • Two Form C normally-closed trouble relays for AC Trouble and General Trouble, Ground Fault relay available on Canadian models only
  • 6 or 10 amp full load output, respectively, with 3 A maximum/circuit
  • Individual NAC power and trouble LEDs for diagnostic efficiency
  • Trouble history modes for diagnostic support
  • Wide range end-of-line supervision value (normal: 2K-27K ohms)
  • Selectable earth fault detection (enable or disable)
  • AC trouble report delay timer
  • Completely configurable via onboard DIP switches, no extra software required
  • Self-contained in compact, locking cabinet constructed of heavy gauge steel with a corrosion-resistant powder coat chip and scratch-resistant finish
  • Cabinet designed with ten double knockouts and a removable door for ease of installation and wiring
  • Includes integral battery charger capable of charging up to 33 AH batteries
  • Cabinet can house two 7 AH or 18 AH batteries
  • Battery charger may be disabled via DIP switch for applications requiring larger batteries and external battery charger
  • Removable terminal blocks accommodate up to 12 AWG (3.1mm 2 ) wire
  • Works with any UL 864 FACP which utilizes an industry-standard reverse-polarity notification circuit
  • Optional devices include addressable control, monitor, and relay modules and power-supervision relay (EOLR-1)
Standards and Codes

The PSE Series comply with the following standards:

  • NFPA 72 National Fire Alarm Code
  • UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode), 10th Edition
  • UL 1481 Power Supplies for Fire Alarm Systems
  • IBC 2009 (when using SEISKIT-MULTI-1)
  • CBC 2007 (when using SEISKIT-MULTI-1)
Agency Listings and Approvals

These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL Listed: S635, S674
  • ULC Listed: S635 (PSE-6/10C)
  • CSFM Approved: 7315-0028:0513
  • FDNY Approved
  • FM Approved

Specifications
Primary (AC) Power:PSE-6(C): 120 VAC, 50/60 Hz, 5.0A maximum
PSE-10(C): 120VAC, 50/60 Hz, 6.2 A maximum
PSE-6E: 240 VAC, 50/60 Hz, 2.7A maximum
PSE-10E: 240 VAC, 50/60 Hz, 3.5A maximum
Wire Size: #12-14 AWG with 600 V insulation
Control Input Circuit:Trigger Input Voltage: 9 to 32 VDC
Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9 - 16 V)
Trouble Contact Rating:4A at 24 VDC
Output Circuits:PSE-6: TB8-TB9 – 1A Regulated, 3A special applications; TB10-TB12 – 0.3A Regulated, 3A special applications
PSE-10: TB8-TB11 – 1.5A Regulated, 3A special applications; TB12-TB14 – 0.3A Regulated, 3A special applications
6.0 A (PSE-6) or 10.0 A (PSE-10) maximum total continuous current for all outputs
Secondary Power (Battery) Charging Circuit:Supports lead-acid batteries only
Float-charge voltage: 27.6 VDC
Maximum current charge: 1.5 A
Maximum battery charging capacity: 33 AH (external cabinet)
Dimensions:20.0”H x 14.5”W x 3.5”D (cm: 50.8H x 36.83W x 8.9D)
Weight:with two 7Ah batteries is 24 pounds (10.9 kg), with two 18 AH batteries is 39 pounds (17.7 kg)
Export Info
Made inUnited States

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer/Electronic Payment and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> NOTIFIER :    42 Items found.
HS-NCM-MF__
(4326)

NOTIFIER  HS-NCM-MF

Notifier HS-NCM High-Speed Network Communications Module. Single or Multi-mode versions available. Allow connection from Notifier Panels to NOTI•FIRE•NET with a fiber-optic cable or twisted-pair wire. NFPA Style 4 (Class B) or Style 7 (Class A) operation. 24 VDC, 100Mb baud transmission rate. UL, ULC, CSFM and FM approved.

CPU2-3030D
(6931)

NOTIFIER  CPU2-3030D

Notifier CPU2-3030D Central processing unit for an NFS2-3030 system. Keypad/display installed; includes 640-character backlit LCD display, QWERTY programming and control keypad. Requires an AMPS-24(E) power supply.