Honeywell Xnxutaennnnn-xnxxsc1ss | Carbon Monoxide | Gas Detectors (explosion-proof) | Gasdetectorsusa
Gas Leak and Flame Detectors, Analyzers, Alarm Devices and Calibration Gas

HONEYWELL   XNXUTAENNNNN-XNXXSC1SS

HONEYWELL XNXUTAENNNNN-XNXXSC1SS
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
Honeywell XNX Universal Gas Detector Transmitter for monitoring Carbon Monoxide (CO) 0-300ppm, user adjustable (100 to 999ppm, 100ppm increments) compatible with all Honeywell gas sensing technologies with aluminum housing. 3-wire 4-20mA HART loop, backlit LCD Display, option for Modbus, Foundation H1 Fieldbus, local Hart and relay outputs UL Certified Class 1, Div 1 Groups A, B, C, D / ATEX Zone 1, SIL-2

XNXUTAENNNNN-XNXXSC1SS   
1,969.63

Agency Approval & Entry Threads
Enclosure
Interface option
Local HART Port
Custom Tag

   4 Weeks  ]



The XNX Universal Transmitter marks a new turn in gas detection from Honeywell Analytics. It supports the widest range of sensors on a common platform and offers a modular choice of inputs and outputs.

FEATURES

High performance
  • Flammable gas detection 0 to 100% LFL/LEL
  • Point IR with heated optics provides immunity to poisoning and no hidden faults
  • Open-path IR flammable gas detection in LEL-m measurement
  • Electrochemical cell offers toxic gas detection in ppm
  • IR cell provides CO2 and combustible gas monitoring
  • Robust and reliable operation in explosive areas and harsh environments
Flexible Operation
  • 3 versions - supports mV (Catalytic Bead and IR Cell), Electrochemical Cell and IR (point and open-path) gas detection
  • Multi-Purpose Detector (MPD) with field serviceable mV, Catalytic bead and IR Cell capability
  • 4-20mA with HARTŽ as standard
  • Multiple communications options include up to 3 relays, MODBUSŽ and FOUNDATIONŽ H1 Fieldbus (pending)
  • Optional local IS port for handheld HART configurator
Easy to Use
  • Large, backlit, easy-to-view LCD display offers multisensory indicators (visual icons, colored buttons, text, etc.) to display gas and sensor readings
  • User interface supported by 8 selectable languages (English, Spanish, German, Italian, Portuguese, French, Russian, Chinese)
  • Self-test and fault indication features
  • Non-intrusive, one-man operation
  • Quick calibration with auto-inhibit
Easy to Install
  • 3 or 4 wire operation, source, sink or isolated
  • Use with conduit or cable installations
  • Simple plug-in sensors and replaceable cells
  • NEMA 4X IP66 rated for rugged indoor/outdoor use
Cost Effective
  • Minimal training required
  • One-man operation
  • Plug-in sensor replacement
  • All necessary accessories included
Applications
  • Offshore Oil & Gas production platforms
  • Onshore Oil terminals
  • Refineries
  • Gas Transmission
  • Gas Distribution
  • LNG terminals
  • Gas storage terminals
  • Chemical plants
  • Petrochemical plants
  • Solvent recovery operations

XNX is designed for flexible integration, simple installation, user friendly operation and straightforward maintenance. It is ideal for use with a range of gas monitoring controllers or industry standard PLCs. Users are assured of being protected in all conditions with Honeywell Analytics gas monitoring solutions.

Bringing together the best solutions in gas detection

Electrochemical
  • Proven electrochemical sensing technology
  • Surecell™ electrochemical cells are ideal for hot and humid environments
  • Long life sensing cells (typical >2 years)
  • Patented 'Reflex' sensing element verification diagnostics
  • Sensor recognition software auto configures transmitter
  • Plug and play factory configured sensors
  • Intrinsically safe sensor connection permits hot swap, reducing down time
XNX Surecell Electrochemical sensors

XNX's modular design enables Honeywell Analytics to offer appropriate, cost effective solutions to a wide range of gas detection requirements.

With the XNX, you are freed from the need to add extra controllers, junction boxes, relays, monitors and other equipment accessories.

The XNX Universal Transmitter is an excellent choice for those who want a total integrated monitoring and safety solution for an industrial plant.

The XNX's powerful advanced communications module adds increased functionality and flexibility to a gas detection network. Standard HART communications, along with optional Modbus, Foundation Fieldbus (pending) or relays, interface with a PLC and a host of other protocol compatible devices found in industrial applications.

XNX Output Options

Back-lit, easy-to-read LCD display with icons includes a broad range of language options including English, Spanish, French, Italian, Portuguese, German, Russian and Chinese to meet global requirements.

Ordering Information

The XNX part numbering system contains all necessary information to convey the product configuration including options. Agency, Port Thread, Enclosure Material, Sensor Personality define the standard unit. Three option fields are used to define optional Relay or Fieldbus interfaces and factory installed local HARTŽ. To order XNX parts, call 800-538-0363.

XNX Order Information Matrix

XNX Transmitter
Material LM25 Aluminum, painted (SS316 painted optional)
Cable Entries 5 conduits/cable entries – (2 right, 2 left, 1 bottom) Available in ž" NPT, or M25
Termination Cage Clamp pluggable Terminal Blocks with retaining screws, 0.5 to 2.5mm (12-28 AWG)
Mounting XNX Enclosure Bracket (ears on casting for u-bolt). Integral cast mounting flanges provide secure mounting to surfaces, channels or up to 6" Pipe.
Optional Remote sensor (up to 50 ft / 15.2 M) for Cat Bead and Toxic
User interface Standard Custom Backlit LCD. 2.5" High Resolution DOT Matrix Display. Discrete Alarm and Status indication. Reliable Non-Intrusive 4 button interface magnetic wand access. Optional HART Handheld with IS Port
Signal Standard HART over 3-wire 4-20mA (sink or source). Optional Modbus over RS-485 and Foundation Fieldbus
Environmental
Temperature -40°C to +65°C / -40°F to +149°F (sensor dependent)
Humidity 20 to 90% RH non-condensing
IP Rating NEMA 4X IP65
Options
  Form C and SPDT 3 Relays, 240 VAC, 5A (2 Alarm, 1 Fault) (Mutually exclusive with Modbus and Fieldbus Options)
Power
  18V to 32V (24V nominal)
Hazardous Area Approvals
 
Performance Approvals UL Certified Class 1, Div 1
ATEX Zone 1
Display Module & User Interface (Standard)
Display Type Backlit LCD
Information Displayed
Base Information: Gas Reading
Gas Name and Units of measurement
Fault and Alarm Status
Large Numeric concentration or LEL display
Bar graph showing current reading, set points and full scale.
Fault/Alarm and Operating Status Indication: Security settings allow multi level operator access for set-up, configuration and calibration
Event history stores Time and Date of all Alarm, Diagnostic, Configuration events
Interface Magnetic wand with terminal screwdriver (supplied each unit)
4-20mA & HART (Standard Supply)
Description Fully configurable isolated 4-20mA & HART output module providing current sink, current source and isolated modes of operation. (supports HART 6.0 protocol)
Non-intrusive Interface Optional local IS port to enable HOT connection of a HART handheld configurator
Operating Modes Current sink / Current source / Isolated current sink /Conventional or with HART data
Output Range 0 to 22mA
4-20mA Signal Accuracy +/- 1% FS
Max loop resistance 600 Ohms at 24Vdc loop supply
Functions Supported via HART
Gas Reading Detailed Sensor Information Including: RTC (Excel Only)
Gas Name and Units of measurement 4-20mA signal level Optical Signal Level Calibration and Configuration status
General/Device Information Dynamic Reserve (Excel Only) Detailed Fault and Warning Information
Installation Raw reading Fault and Alarm History
Configuration Temperature
Forcing of 4-20mA output
Local IS HART Port (Optional)
Description Provides externally accessible IS connections to the XNX transmitter to enable HOT connection of HC275/375 HART or equivalent hand held configurator.
Installation Fitted to one of the cable entries on the XNX transmitter.
Environmental Protection Terminals protected by cover to IP 66 when not in use
Relay Module (Optional)
Description Provides three fully user configurable relay outputs that can be switched based on the current gas level and/or status of the transmitter. Provides 2 x SPCO alarm and 1 x SPCO fault relays. Single Pole Double Throw SPDT. Option PCB Factory installed in display module.
Installation Fitted into housing base either at the factory or in the field by qualified service engineer.
Rating
Maximum: 240VAC, 5A (non inductive load) Minimum: 5V, 10mA (non inductive load)
Electrical Connections Fault: Common, Normally Open, Normally Closed
Alarm 1: Common, Normally Open, Normally Closed
Alarm 2: Common, Normally Open, Normally Closed
Configuration
Default Configurable Options
Fault Relay: Fault Relay:
Normally energized Normally energized / normally de-energized
Non latching None
Signal inhibit as fault Enable/disable
Alarm 1 / 2 Relays: A1 / A2 Relays:
Normally de-energized Normally energized / de-energized
Non latching Latching / non latching
Alarm rising on gas reading Alarm on rising / falling
Alarm level 20% and 40% of scale Alarm level 10% to 90% of full scale
Hysteresis of 2% of scale
Re-setting of Latched Relays Easily accessible interface on display (if used) or via HART interface (local or remote)
Note Use of the Relay Module or 'Other' Communications Module (E.g. Foundation Fieldbus) is mutually exclusive. However, relay function may be used in conjunction with standard communication output i.e. 4-20mA with HART.
Relay Specific Functions via HART Interface Relay status information / Reset of latched conditions / Configuration of relays Forcing of relay state
Reset through non intrusive User Interface. Remote Switch closure using Remote Reset input Remotely through HART
Foundation Fieldbus Module (Optional)
Description Foundation Fieldbus compliant digital communications interface enables connection of the XNX transmitter to a multi-drop Foundation Fieldbus H1 network.
Installation Fitted into housing base either at the factory or in the field by qualified service engineer.
Connections Sig+, Sig- and Screen
Physical Layer Conforms to IEC 1158-2 and ISA 50.02, 31.25Kbits/s
Maximum No. of Nodes 32
Functions Supported
Gas Reading Detailed Sensor Information Including: Detailed Fault and Warning Information:
Gas Name and Units of measurement Optical Signal Level Fault and Alarm History
Instrument status (OK, warning, fault, over-range) Dynamic Reserve (Excel Only) Zero Calibration
Remote zero and span calibration (detector dependent) 24V supply voltage
Remote zero and span calibration (detector dependent) Temperature
  RTC (Excel Only)
  Calibration and Configuration status
Modbus RTU Module (Optional)
Description The Modbus output module provides an Isolated RS485 output to enable the connection of the XNX transmitter to a multi-drop Modbus network
Installation Fitted into housing base either at the factory or in the field by qualified service engineer.
Connections RS485+, RS485-, Drain
Physical Layer Isolated RS485, 1200 to 19.2K Baud
Maximum No. of Nodes 254 XNX compatible transmitters only
Protocol Modbus RTU
Functions Supported As per Foundation Fieldbus Module (Optional) - see above
Export Info
Made inUnited States
Harmonized Tariff Code (HTC)9027102000

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> ACCESSORIES - RELATED - CONSUMABLES :    9 Items found.
SPXCDWP
(1885)

HONEYWELL  SPXCDWP

Enclosed weather protection housing with bump port for Honeywell XNX.



$103.68 
02000-A-1635
(1881)

HONEYWELL  02000-A-1635

Honeywell Weatherproof cap for use with Toxic/Oxygen detector including remote gassing nozzle (for Toxic Sensepoint Zareba and Sieger, Signalpoint, Satellite -with adapter-, XNX MPD, Series 2000 and 705 sensors)



$110.94 
CYL-10125000
(1275)

PORTAGAS  CYL-10125000

Calibration Gas Carbon Monoxide (CO) 50 ppm Balance Air, 100 Liter GAL C-10 Inlet Portagreen Aluminium Cylinder. (Made by Portagas)

Configure

$124.51 
CYL-10159000
(318)

PORTAGAS  CYL-10159000

Calibration Gas Carbon Monoxide (CO) 200 ppm Balance Air, 100 Liter GAL C-10 Inlet Portagreen Aluminium Cylinder. (Made by Portagas)

Configure

$124.51 
CYL-10195010
(1282)

PORTAGAS  CYL-10195010

Calibration Gas Carbon Monoxide (CO) 500 ppm Balance Air, 100 Liter GAL C-10 Inlet Portagreen Aluminium Cylinder. (Made by Portagas)

Configure

$124.51 
(2136)

HONEYWELL  1226A0354

Remote Gassing Kit for XNX transmitters



$245.72 
XNXXSC1SS
(1237)

HONEYWELL  XNXXSC1SS

Replacement Sensor Assembly for Carbon Monoxide (CO) XNX Transmitter. 0-300ppm, user adjustable (100 to 1,000ppm, 100ppm increments)

Configure

$620.01 
S3KRMK
(1884)

HONEYWELL  S3KRMK

Remote Electrochemical EC sensor mounting kit for Honeywell XNX transmitters.

Configure

$700.84 
TPPLBDWA2NNNNNN
(5825)

HONEYWELL  TPPLBDWA2NNNNNN

Honeywell Touchpoint Plus Wall-mounted Alarm Controller for up to 8 gas detection channels (16 w/ expansion unit). Dustproof and waterproof. Polycarbonate ABS Housing (NEMA 4X). Includes touchscreen interface, built-in sounder, 3 alarm relay outputs, datalogging to SD card and remote reset and inhibit inputs. AC or DC supply voltage. Up to 24 relay outputs and 8mA outputs. IP65. UL and CSA approvals (Class I Div 2).

> CARBON MONOXIDE :    36 Items found.
CM-E1
(638)

MACURCO  CM-E1

Macurco CM-E1 Carbon Monoxide gas detector for residential and commercial office environment. Flush or surface mount options, alarm and trouble relays, and 85 dB buzzer. 9-32 VDC input. NFPA 720-2009 and UL 2075 listed. CSFM Approved.



$66.15 
M015-0001-000
(6333)

MPOWER  M015-0001-000

mPower UNI 321 Disposable Single Gas Detector for detection of Carbon Monoxide (CO) 1-500ppm. Up to 36 months of live. Large LCD display will show time remaining or low/high alarm levels when hit, 6 Bright Red Flashing LED, Vibrating and 90dB Audible Alarm Port. IP67, Event Logger, ATEX and UL approval for Class I Div 1.

Configure

$108.80 
BWC2-M
(4265)

BW  BWC2-M

BW Clip portable gas detector 2 year maintenance free for Carbon Monoxide CO. Low alarm set between 25ppm and 50 ppm, High alarm set between 50ppm and 200 ppm. UL approved for Class I Div 1. ATEX, CE, EC and IECEx approved.

M001-0023-000
(5994)

MPOWER  M001-0023-000

mPower UNI MP100 Portable Single Gas Detector for detection of Carbon Monoxide (CO) 0-500ppm to 0-2000ppm. Includes large LCD display, 6 Bright Red Flashing LED, Vibrating and 90dB Audible Alarm Port. IP67, Event Logger, ATEX and UL approval for Class I Div 1.

Configure

$134.40 
PPS+-CO
(6813)

PROSENSE  PPS+-CO

Prosense PPS+-CO Addressable Gas Detector with Electrochemical sensor for Carbon Monoxide (CO) with range 0-300ppm, 0-500ppm or 0-1000ppm. ABS Plastic housing. Modbus RS485 RTU output. IP54. For Parking Garages and Tunnels.

Configure

$214.50 
PPS-RCO
(6811)

PROSENSE  PPS-RCO

Prosense PPS-RCO Addressable Gas Detector with Electrochemical sensor for Carbon Monoxide (CO) with range 0-300ppm. ABS Plastic housing. Relay outputs. IP54. For Parking Garages and Tunnels.



$214.50 
TX1-1
(5965)

INDUSTRIAL SCIENTIFIC  TX1-1

Industrial Scientific Tango TX1 Gas Detector for Carbon Monoxide (CO) 1-1000 ppm. DualSenseŽ Technology. 2-year run time. Includes LCD Display and 100dB audible alarm. Polycarbonate enclosure. IP66 & IP67. ATEX, CSA, IECEx, UL & INMETRO Approvals.

BWC2R-M
(5149)

BW  BWC2R-M

BW Clip Real Time portable gas detector with 2 year maintenance free for Carbon Monoxide (CO). Configurables Low and high alarm (ppm). One-button operation. Designed for harsh environments and extreme temperatures. Includes a real-time gas level display. IP66 / IP67. UL approved for Class I Div 1. ATEX, CE, EAC Ex and IECEx approved.

BWC3R-M
(5153)

BW  BWC3R-M

BW Clip Real Time portable gas detector with 3 year maintenance free for Carbon Monoxide (CO). Configurables Low and high alarm (ppm). One-button operation. Designed for harsh environments and extreme temperatures. Includes a real-time gas level display. IP66 / IP67. UL approved for Class I Div 1. ATEX, CE, EAC Ex and IECEx approved.

LC-1112-A-000-1
(2913)

INTEC  LC-1112-A-000-1

Intec Controls PolyGard LC-1112 V3 Analog Gas Transmitter for Carbon Monoxide (CO) 0-150 / 0-200 / 0-250 / 0-300 ppm. 1 4-20mA & 2-10V analog output. Wall mounted. NEMA 4X Enclosure. UL Listed and CSA Certified.

Configure

$327.00 
BWS1-ML-Y
(6383)

BW  BWS1-ML-Y

BW Solo Serviceable Single-gas Detector for Carbon Monoxide (CO) 0-2000 ppm. Small and lightweight. One button operation, 3.6V 1.65Ah Lithium Battery. Visual, vibrating and audible alarms. Optional wireless version. IP66/68. ATEX, IECEx and CSA approvals for Class I Div 1.

PC3-4424
(6802)

PROSENSE  PC3-4424

Prosense PC3-4424 Gas Detector with Electrochemical sensor for Carbon Monoxide (CO) with range 0-300 ppm. Epoxy painted aluminum housing and Nickel Plated Brass sensor head. 4-20mA Analog and Modbus RS485 RTU outputs. Optional Relay Outputs. IP65, Zone 2.

Configure

$463.32 
CM-6
(637)

MACURCO  CM-6

MACURCO CM-6 low voltage gas detector, controller and transducer for Carbon Monoxide (CO) 0-200 ppm. Selectable 4-20 mA output, buzzer, alarm and fan relays with digital display. 12 to 24 VAC or 12 to 32 VDC power. ETL Listed to UL 61010-1. Optional LADBS approval.

Configure

$481.90 
CM-12
(3415)

MACURCO  CM-12

MACURCO CM-12 line voltage Gas Detector, controller and transducer for Carbon Monoxide (CO) 0-200 ppm. Selectable 4-20mA output, buzzer, alarm and fan relays with digital display. 100 to 240 VAC 50-60Hz power. ETL Listed to UL 61010-1.

Configure

$494.01 
P-4434
(6777)

PROSENSE  P-4434

Prosense P-4434 Gas Detector with Electrochemical sensor for Carbon Monoxide (CO) with ranges 0-300ppm to 0-1000ppm. Ex-proof housing and SS316 stainless steel sensor head. 4-20mA Analog and Modbus RS485 RTU outputs, optional Relay card. ATEX/IECEx approval (Zone 1 or Zone 2). IP65, Optional IP66 Adaptor.

Configure

$540.54 
364-455-01-365-796-110100
(6150)

DELPHIAN  364-455-01-365-796-110100

Delphian GazTell Fixed Point Electrochemical Gas Detector for Carbon Monoxide (CO) 0-100, 0-300 or 0-1000 ppm. 4-20mA Output. Optional Modbus RTU Output and Alarm Relays. SIL2 Approval. Suitable for Class I Div 1 & 2 Groups C, D.

SPSTAXC1
(1477)

HONEYWELL  SPSTAXC1

Honeywell Zareba Sensepoint Gas Detector Transmitter for Carbon Monoxide (CO) with pre-wired universal junction box (1 threaded M20, 1 clearance 3/4"NPT, 1 clearance 1/2" NPT, 3 approved stopping plugs, earth continuity plate) and factory set toxic gas sensor. 2 wire 4-20mA loop output. ATEX Approved. (Optional ranges: 0-200 ppm, 0-500 ppm)

Configure

$719.15 
PQN-4434-1/2
(6949)

PROSENSE  PQN-4434-1/2

Prosense PQN-4434 Gas Detector with Electrochemical sensor for Carbon Monoxide (CO) with ranges 0-300ppm, 0-500ppm or 0-1000ppm. Ex-proof housing and SS316 stainless steel sensor head. 4-20mA Analog and Modbus RS485 RTU outputs, optional Relay card. ATEX/IECEx (Zone 1, Zone 2 or M2), UL/CSA (Class I Div 1), UKCA or INMETRO approval, optional SIL2. IP65, Optional IP66 Adaptor and remote display.

Configure

$720.72 
OI-6000-EC-CO-X-R_-DC-C
(6832)

OTIS  OI-6000-EC-CO-X-R-DC-C

Otis Instruments OI-6000 Gas Leak Detector with electrochemical sensor for Carbon Monoxide (CO) 0-1000ppm. Non explosion proof. Wired power (3-Wire) (12 to 35 VDC) with 4-20 mA analog, RS-485 Modbus and 2 relay outputs. 3 Push-Button Interface. IP 66/67. Optional radio. UL Approved.

PQD-4434-1/2
(6738)

PROSENSE  PQD-4434-1/2

Prosense PQD-4434 Gas Detector with Electrochemical sensor for Carbon Monoxide (CO) with ranges 0-300ppm, 0-500ppm or 0-1000ppm. Ex-proof housing and SS316 stainless steel sensor head. 4-20mA Analog and Modbus RS485 RTU outputs, optional Relay card. OLED Display. ATEX/IECEx (Zone 1, Zone 2 or M2), UL/CSA (Class I Div 1), UKCA or INMETRO approval, optional SIL2. IP65, Optional IP66 Adaptor.

Configure

$875.16 
OI-6000-EC-CO-X-X-O
(6835)

OTIS  OI-6000-EC-CO-X-X-O

Otis Instruments OI-6000 Gas Leak Detector with electrochemical sensor for Carbon Monoxide (CO) 0-1000ppm. Explosion Proof Wired power (3-Wire). (12 to 35 VDC) with 4-20 mA analog and RS-485 Modbus outputs. 3 Push-Button Interface. IP 66/67. Optional alarm relays and Radio. CSA Approved for Class I Div 1. ATEX Zone 1 and IECEx Certified.

GG-CO-200
(2963)

CALIBRATION TECHNOLOGIES  GG-CO-200

CTI GasGuard CO Carbon Monoxide Electrochemical Sensor (0-200 ppm) for gas leak detection in food processing areas, warehousestank rooms and others. No false alarms. 4-20 mA output, 24VDC power supply and NEMA 4X polycarbonate enclosure.

Configure

$1,122.00 
2106B1405
(1453)

HONEYWELL  2106B1405

Honeywell Sieger Sensepoint Gas Detector Transmitter for Carbon Monoxide (CO) (0-100 to 0-500) ppm with Surecell Toxic Sensor. 2 wire 4-20mA loop output. ATEX/IECEx CSA Class I Division 2 Certified.

Configure

$1,135.98 
1100ALD-109011/0100P-L0
(6909)

RC SYSTEMS  1100ALD-109011/0100P-L0

RC Systems SenSmart 1100 gas detector for Carbon Monoxide (CO) 0-100ppm to 0-5000ppm with 'ST-48' smart transmitter. Electrochemical sensor. 2-Wire 4-20mA output. 10-30 VDC. Aluminum or Stainless Steel enclosure. CSA certified for Class 1 Div 1 (Explosion Proof).

Configure

$1,314.28 
GG-CO-200-EXP
(5976)

CALIBRATION TECHNOLOGIES  GG-CO-200-EXP

CTI GG-CO-EXP Explosion Proof Electrochemical Gas Sensor for Carbon Monoxide (CO) 0-200 ppm. 4-20 mA output, 24VDC power supply. Explosion Proof Copper-free aluminum enclosure for Class l, Div 1 & 2, Groups B, C & D. CSA, UL, FM, ATEX and IECEx approved.

Configure

$1,383.00 
100-0008-SS/100-0015-CO
(4751)

ESP SAFETY  100-0008-SS/100-0015-CO

ESP Safety Vector 2-channel gas detector controller with smart Plug-In sensor included to detect Carbon Monoxide (CO) 0-100, 0-500 or 0-1000ppm. Operates as a stand-alone display for a variety of ESP sensors which can be remotely located up to 500 feet away over 4-wire RS-485. Sensor head can also be attached. Includes analog 4-20 current loop with HART, Digital RS-485 Modbus RTU and 4 relays. 96-Character OLED Screen. 316 Stainless Steel or Aluminum Explosion-proof housing. IP67. SIL 2, FM/CSA Class I Division 1 certification. Optional 2nd sensor available.

Configure

$1,440.00 
SPXCDULNCX
(664)

HONEYWELL  SPXCDULNCX

Honeywell XCD Sensepoint Gas Detector, Carbon Monoxide (CO) Electrochemical Sensor with aluminium housing (optional stainless steel), stainless steel sensor head, tri-color backlit LCD Display, explosion-proof IP66 for carbon monoxide (CO) gas hazards both indoors and outdoors. 3-wire 24 VDC power, include 2 programmable alarm relays, 1 programmable fault relay, 4-20mA output (sink or source selectable); Modbus RTU option available. User-Selectable full scale range 100 to 1,000ppm. UL/CSA Class I Division 1 or ATEX (Zone 1) IECEx available.

Configure

$1,442.71 
S3KUL2-XNXXSC1SS
(686)

HONEYWELL  S3KUL2-XNXXSC1SS

Honeywell Series 3000 MkII Gas Detector Transmitter, with aluminum housing (optional stainless steel) for monitoring CARBON MONOXIDE (CO) with electrochemical sensor, 2-wire 4-20mA loop, LCD Display, 0-300ppm, user adjustable (100 to 999ppm, 100ppm increments) Available Approvals UL Class I, Div 1 & 2, ATEX Zone 0 and IECEx.

Configure

$1,497.56 
41001AL-0-1011/0050P/L0
(7159)

RC SYSTEMS  41001AL-0-1011/0050P/L0

RC Systems SenSmart 4100 2-wire 4-20mA loop powered gas detector for Carbon Monoxide (CO) 0-50 to 0-5000ppm with GEN 2 smart Electrochemical sensor. Includes LCD Display. 10-30 VDC, Two flashing Alarm LEDs. Aluminum, Stainless Steel or non-metallic enclosure. CSA certified for Class 1 Div 1 & 2 (Explosion Proof).

Configure

$1,538.96 
961-440026-100G
(2131)

DETCON  961-440026-100G

Detcon DM-100-CO Electrochemical Carbon Monoxide (CO) 0-100ppm SensorAssembly with optional loop powered display. 4-20 mA. Features intelligent electronices, non-intrusive operator interface and comprehensive fault diagnostics. Optional 316 Stainless Steel Housing. 3/4" NPT thread. XP-instrinsically safe. Class I, Div. 1, Groups A, B, C, & D.

51001AL-0-1011/0050P/L0
(7124)

RC SYSTEMS  51001AL-0-1011/0050P/L0

RC Systems SenSmart 5100 3-wire gas detector for Carbon Monoxide (CO) 0-50 to 0-5000ppm with GEN2 smart sensor, Color backlit LCD Display and 4-20mA output, 10-30 VDC. Aluminum or Stainless Steel enclosure. CSA Class I Division 1 (Explosion-Proof). Optional 2 RS-485 Modbus ports, 2 Programmable Alarm and Fault Relays.

Configure

$1,594.80 
967-444490-0100
(6074)

DETCON  967-444490-0100

Detcon DM-700-CO Electrochemical Smart Carbon Monoxide (CO) 0-100 ppm/0-200 ppm Sensor Assembly with LED display. 4-20mA and Modbus RS-485 outputs. 316 Stainless Steel Housing. Water Proof, Corrosion Proof, Vibration Proof and Explosion proof. NEMA 4X. IP66. Class I, Div. 1, Groups B, C, & D. CSA and ATEX approvals.

SPXCDULNC2
(5096)

HONEYWELL  SPXCDULNC2

Honeywell Sensepoint XCD RTD Gas Detector for Carbon Monoxide (CO) with Electrochemical Sensor. Aluminium alloy LM25 or 316 stainless steel housing, PPS sensor head, tri-color backlit LCD Display. IP67. 3-wire 24 VDC power. Includes 3 programmable alarm relays and 4-20mA output (sink or source selectable), Modbus RTU option available. User-Selectable full scale range 0 to 200 ppm. UL/cCSAus Approved for Class I Div 2. Remote Sensor Option.

Configure

$1,735.82 
2100AL-0-9011/0100P/L0
(117)

RC SYSTEMS  2100AL-0-9011/0100P/L0

RC Systems SenSmart 2100 2 wire 4-20mA Loop Powered gas detector for Carbon Monoxide (CO) 0-100ppm to 0-5000ppm with 'ST-48' smart transmitter. Includes Graphic LCD Display, LED indicator and 4-20mA output. 10-30 VDC. Stainless steel or aluminum enclosure. CSA certified for Class 1 Div 1 & 2 (Explosion Proof).

Configure

$1,789.61 
31001AL-0-9011/0100P/L0
(5780)

RC SYSTEMS  31001AL-0-9011/0100P/L0

RC Systems SenSmart 3100 3 wire gas detector for Carbon Monoxide (CO) 0-100ppm to 0-1000ppm with 'ST-48' smart transmitter. Includes Graphic LCD Display, LED indicator and 4-20mA output, optional alarm relays and Modbus RTU. 10-30 VDC. Aluminum or Stainless Steel enclosure. CSA certified for Class 1 Div 1 (Explosion Proof).

Configure

$1,967.53 
6100AL1-0-1011/0050P
(7002)

RC SYSTEMS  6100AL1-0-1011/0050P

RC Systems SenSmart 6100 3 wire Dual Channel Gas Detector for Carbon Monoxide (CO) 0-50 to 0-5000ppm with 'ST-44' smart transmitter and GEN2 smart sensor. Includes Color TFT Display, 4-20mA output. OPTIONAL two RS-485 Modbus ports, embedded Ethernet with Webserver, Modbus TCP, 2 Alarm + Fault Relays. 10-30 VDC. Aluminum, Stainless Steel or Poly enclosure. CSA certified for Class 1 Div 1 (Explosion-Proof). IP66.

Configure

$2,389.61 
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.