Notifier Sd365 | Intelligent | Smoke | Gasdetectorsusa
Gas Leak and Flame Detectors, Analyzers, Alarm Devices and Calibration Gas

NOTIFIER   SD365

SKU# (7235)
NOTIFIER SD365
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
Notifier SD365 Addressable Photoelectric Smoke Detector. Two-wire SLC loop connection. LiteSpeed and CLIP protocol. UL/ULC and FM Approved.

UL   FM

Please Email us your request for quote   

   2 Weeks  ]

The Fire•Lite® Alarms SD365(A), SD365R(A), and SD365HT(A) intelligent plug-in smoke detectors are designed for both performance and aesthetics, and are direct replacements for the SD355 Series. A new modern, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards.

Exclusively for use with Fire•Lite’s addressable fire alarm control panels, the SD365(A) Series point ID capability allows each detector’s address to be set with rotary, decimal address switches, providing exact detector location for emergency personnel to quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication.

The SD365(A) Series also offers 135°F (57°C) fixed temperature thermal sensing on the SD365T(A) and a remote test capable detector on the SD365R(A) for use with DNR(A)/DNRW duct smoke detector housings.

Features SLC LOOP:
  • Two-wire SLC loop connection
  • Unit uses base for wiring
  • Compatible with LiteSpeed™ and CLIP protocol systems
  • Stable communication technique with noise immunity
ADDRESSING:
  • Addressable by device
  • Rotary, decimal addressing (Refer to the Fire•Lite panel manuals for device capacity.)
ARCHITECTURE:
  • Sleek, low-profile, stylish design
  • Unique single-source design to respond quickly and dependably to a broad range of fires
  • Integral communications and built-in device-type identification
  • Built-in tamper resistant feature
  • Remote test feature from the panel
  • Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(LiteSpeed systems only)
  • Built-in functional test switch activated by external magnet
  • Removable cover and insect-resistant screen for simple field cleaning
  • Expanded color options
OPERATION:
  • Designed to meet UL 268 7th Edition
  • Factory preset at 1.5% nominal sensitivity for panel alarm threshold level
  • LED “blinks” when the unit is polled (communicating with the fire panel) and latches in alarm.
  • Low standby current
MECHANICALS:
  • Sealed against back pressure
  • SEMS screws for wiring of the separate base
  • Designed for direct-surface or electrical-box mounting
  • Plugs into separate base for ease of installation and maintenance
  • Separate base allows interchange of photoelectric, ionization and thermal sensors
OPTIONS:
  • Optional relay, isolator, and sounder bases
Installation

SD365 Series plug-in intelligent smoke detectors use a detachable base to simplify installation, service and maintenance. Installation instructions are shipped with each detector.

Mount detector base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DF-60059.

NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Class “B” wiring only. When using relay or sounder bases, consult the I300(A) installation sheet I56-3626 for device limitations between isolator modules and isolator bases.

Construction

These detectors are constructed of fire-resistant plastic. The SD365 Series plug-in intelligent smoke detectors are designed to commercial standards and offer an attractive appearance.

Operation

Each SD365 Series detector uses one of the panel’s addresses (total limit is panel dependent) on the Fire•Lite Signaling Line Circuit (SLC). It responds to regular polls from the control panel and reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The SD365 Series offers features and performance that represent the latest in smoke detector technology.

Detector Sensitivity Test

Each detector can have its sensitivity tested (required per NFPA 72, Chapter 14 on Inspection, Testing and Maintenance) when installed/ connected to an Fire•Lite addressable fire alarm control panel. The results of the sensitivity test can be printed for record keeping.

DETECTOR SPACING AND APPLICATIONS

Fire•Lite recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet (9.1m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. A System Smoke Detector Application Guide, document SPAG91, is available at www.systemsensor.com.

Listings and Approvals

Listings and approvals below apply to the SD365 Series detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status

  • UL/ULC Listing: S1059
  • FM Approved
  • CSFM: 7272-0075:0502

SYSTEM SPECIFICATIONS
Sensitivity:UL Applications: 0.5% to 4.0% per foot obscuration.
ULC Applications: 0.5% to 3.5% per foot obscuration
Size:2.0" (51mm) high; base determines diameter
– B300-6: 6.1" (15.6 cm) diameter
– B501: 4" (10.2 cm) diameter
For a complete list of detector bases see DF-60983
Shipping weight:3.4 oz. (95 g)
Operating temperature range:SD365: 32°F to 122°F (0°C to 50°C)
SD365T Series: 32°F to 100°F(0°C to 38°C)
SD365R Series installed in a DNR/DNRW, -4°F to 158°F (-20°C to 70°C)
UL/ULC Listed Velocity Range:0-4000 ft/min. (1219.2 m/min.), suitable for installation in ducts
Relative humidity:10% – 93% non-condensing
Thermal ratings:fixed-temperature set point 135 ° F (57°C), rate-of-rise detection 15°F (8.3°C) per minute, high temperature heat 190°F (88°C)
ELECTRICAL SPECIFICATIONS
Voltage range:15 - 32 volts DC peak
Standby current (max. avg.):200µA @ 24 VDC (o ne communication every 5 seconds with LED enabled)
Max current:4.5 mA @ 24 VDC (“ON”)
Export Info
Made inMexico
Harmonized Tariff Code (HTC)8531100025

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer/Electronic Payment and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> INTELLIGENT :    24 Items found.
FCO-951
(3502)

NOTIFIER  FCO-951

Notifier IntelliQuad PLUS FCO-951 Advanced Multi-Criteria Fire/CO Detector with four unique sensing elements: Carbon Monoxide (CO) electrochemical sensor, Infrared (IR) sensing measure, Photo-electric smoke detection and Thermal detection. UL listed. *** replaces FSC-851 ***



 
FSV-951R
(3229)

NOTIFIER  FSV-951R

Notifier FSV-951R Series Very Intelligent Plug-in Early Warning (VIEW) Laser Smoke Detector. 0.03% to 1.00% (CLIP) or 0.02% to 2.00% (other) sensivity. With FlashScan and CLIP protocol systems. Advanced laser light source and 360° viewing angle. Optional relay, isolator and sounder bases. UL and MEA listed. FM, CSFM, BSMI and CCCF Approved. (replaces FSL-751)

4098-9756
(7075)

SIMPLEX TYCO  4098-9756

Simplex Tyco 4098-9756 Addressable Duct Sensor Housing with TrueAlarm Photoelectric Smoke Sensor. Includes relay, supervised output for multiple remote relays and 2 diagnostic LEDs. IDNet and MAPNET II communications. UL listed (requires separate 24 VDC fire alarm power).



 
FS-OSI-RI
(6933)

NOTIFIER  FS-OSI-RI

Notifier FS-OSI-RI Intelligent Addressable Single-ended Reflective Imaging Beam Smoke Detector suited for large open areas with high ceilings. 24 VDC. 12° field of view. Status LED indicators. UL and FM approved.



 
Page: 1 | 2 | All