Simplex Tyco 4098-9612 | Intelligent | Thermal | Gasdetectorsusa
Gas Leak and Flame Detectors, Analyzers, Alarm Devices and Calibration Gas

SIMPLEX TYCO   4098-9612

SKU# (6854)



SIMPLEX TYCO 4098-9612
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
Simplex 4098-9612 Electronic Heat Detector for Two-Wire Direct Connect with fixed temperature operation. 15 to 32 VDC. Thermistor based. Non-Addressable Initiation. Ceiling or wall mounting. LED alarm. UL, CSFM Listed and FM Approved.

4098-9612   
Please Email us your request for quote   

Version

   4 Weeks  ]
Features Accurate and reliable heat detection for protection of property** UL listed to Standard 521 Fixed temperature operation is suitable for most applications:
  • Thermistor based design is inherently rate compensated due to minimal thermal lag
  • Available for 135° F (57° C) or 200° F (93° C)
  • UL and ULC spacing distance is 70 ft (21.3 m)
Available with rate-of-rise temperature detection:
  • Dual thermistor rate-of-rise operation
  • For use where anticipated ambient temperature changes are less than 6° F/minute (3.33° C/minute)
  • UL and ULC spacing distance is 70 ft (21.3 m)
Epoxy encapsulated electronic design provides:
  • Operation for ceiling or wall mounting
  • Easily tested, self-restoring operation with repeatable accuracy
  • Alarm indicating LED located on detector
  • Current limited alarm that is compatible with two-wire initiating device circuits (IDCs)
  • Designed for EMI compatibility
Direct connecting design:
  • Wiring attaches directly to detector terminals
  • Detector mounts onto mechanical adapter plate (supplied)

Accurate Electronic Design. Simplex electronic heat detectors use a fast response, thermistor based design to provide temperature sensing that quickly, accurately, and consistently identifies when fixed temperatures are exceeded. The fixed temperature sensing thermistor readily tracks the local ambient temperature. This eliminates the time required to melt a lead pellet or heat a bimetallic element as occurs in mechanical heat detector designs and provides the required heat detection for most applications.

Rate-of-rise detection is determined by comparing two thermistor responses. By combining accurate thermistors with proper physical placement, this patented rate-of-rise detection design achieves a high level of performance not normally available with mechanical detection.

Applications Reference

Heat detectors are used where property protection is desired and where life safety protection is not required or is performed by other equipment. Typical heat detector applications are satisfied by use of these fixed temperature electronic detectors.

The addition of rate-of-rise operation provides two forms of heat detection for use where temperature fluctuations are controlled and are less than 6° F/min (3.33° C/min). Where temperatures may fluctuate more quickly, use fixed temperature detection.

Alarm Indicating LED Operation

The heat detector LED turns ON continuously when in alarm. During normal conditions the LED is OFF.

Fixed Temperature Guidelines

135° F (57° C) fixed temperature detectors are for normal temperatures that do not exceed 100° F (38° C).

200° F (93° C) fixed temperature detectors are for normal temperatures that exceed 100° F (38° C) but are less than 150° F (66° C).

Alarm Verification Application Note

When connecting these electronic heat detectors to a 2-wire initiating device circuit (IDC) that is providing Alarm Verification for smoke detectors, use the 4098-9682, 4-wire base. The 4-wire base provides an alarm contact that is not current-limited. (Heat detectors in the 2-wire base present a current-limited alarm condition that is not compatible with Alarm Verification. Initiating devices other than smoke detectors are required to activate the alarm without starting the alarm verification cycle.)

Specifications
Voltage Range 15 to 32 VDC, filtered DC with 30% maximum ripple
Standby Current 80 A typical, 100 A maximum
Alarm Current, 2-Wire Operation Up to 86 mA maximum, exact current is determined by alarm current limiting of connected IDC
Alarm Current, 4-Wire Operation 24 mA typical @ 24 VDC
Rate-of-Rise Operation Meets FM requirements for operation between 15° and 25° F/min (8.33° and 13.88° C/min)
Humidity Range 10% to 95% RH, not intended for outdoor applications
Storage Temperature 0° to 140° F (-18° C to 60° C)
Color Frost-White
Ambient Temperature Operating Range
135° F Models 32° to 100° F (0° to 38° C)
200° F Models 32° to 150° F (0° to 68° C)

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer/Electronic Payment and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> INTELLIGENT :    24 Items found.
FCO-951
(3502)

NOTIFIER  FCO-951

Notifier IntelliQuad PLUS FCO-951 Advanced Multi-Criteria Fire/CO Detector with four unique sensing elements: Carbon Monoxide (CO) electrochemical sensor, Infrared (IR) sensing measure, Photo-electric smoke detection and Thermal detection. UL listed. *** replaces FSC-851 ***



 
FSV-951R
(3229)

NOTIFIER  FSV-951R

Notifier FSV-951R Series Very Intelligent Plug-in Early Warning (VIEW) Laser Smoke Detector. 0.03% to 1.00% (CLIP) or 0.02% to 2.00% (other) sensivity. With FlashScan and CLIP protocol systems. Advanced laser light source and 360° viewing angle. Optional relay, isolator and sounder bases. UL and MEA listed. FM, CSFM, BSMI and CCCF Approved. (replaces FSL-751)

4098-9756
(7075)

SIMPLEX TYCO  4098-9756

Simplex Tyco 4098-9756 Addressable Duct Sensor Housing with TrueAlarm Photoelectric Smoke Sensor. Includes relay, supervised output for multiple remote relays and 2 diagnostic LEDs. IDNet and MAPNET II communications. UL listed (requires separate 24 VDC fire alarm power).



 
FS-OSI-RI
(6933)

NOTIFIER  FS-OSI-RI

Notifier FS-OSI-RI Intelligent Addressable Single-ended Reflective Imaging Beam Smoke Detector suited for large open areas with high ceilings. 24 VDC. 12° field of view. Status LED indicators. UL and FM approved.



 
Page: 1 | 2 | All