Simplex Tyco 4098-9733 TrueAlarm Analog Heat Sensor with three user-selectable sensitivities. IDNet or MAPNET communications. Remote LED alarm indicator and relay connections. Ceiling or wall mounting. NEMA 1. UL and ULC Approved.

RELAYS   UL

4098-9733   
Please Email us your request for quote   

Version
Place of Assembly
Bases

   2 Weeks  ]
3 Variants of base SKU
Features TrueAlarm analog sensing provides the following features
  • Digital transmission of analog sensor values using IDNet or MAPNET II two-wire communications
For use with the following Simplex products
  • 4007ES, 4010, 4010ES, 4100ES, and 4100U Series control units and 4008 Series control units with reduced feature set (refer to data sheet S4008-0001 for details)
  • 4020, 4100, and 4120 Series control units, Universal Transponders, and 2120 TrueAlarm CDTs equipped for MAPNET II operation
Heat sensors have these features
  • Three fixed temperature sensing thresholds: 135°F, 155°F and 190°F
  • Rate-of-rise temperature sensing
  • Utility temperature sensing
  • Listed to UL 521 and ULC-S530
General features
  • Ceiling or wall mounting
  • Listed to UL 268 7th Edition and ULC-S529
  • NEMA 1 rated. See TrueAlarm analog sensing product selection chart for more information.
  • Louvered smoke sensor design enhances smoke capture by directing flow to chamber; entrance areas are minimally visible when ceiling mounted
  • Designed for EMI compatibility
  • Magnetic testing
  • Different bases support a supervised or unsupervised output relay, or a remote LED alarm indicator
Additional base reference
  • For isolator bases, refer to data sheet S4098-0025
  • For sounder bases, refer to data sheet S4098-0028
  • For photo/heat sensors, refer to data sheet S4098-0024 , single address and S4098-0033 , dual address
Digital communication of analog sensing

TrueAlarm analog sensors provide an analog measurement digitally communicated to the host control panel using Simplex addressable communications. The control unit analyses the data, determines an average value and stores it. Comparing the sensor's present value against its average value and time, determines an alarm or other abnormal condition.

Intelligent data evaluation

Monitoring each sensor's average value provides a continuously shifting reference point. A software filtering process compensates for environmental factors, such as dust and dirt, and component aging, to provide an accurate reference for evaluating new activity. This filtering reduces the probability of false or nuisance alarms caused by shifts in sensitivity, either up or down.

Control unit selection

The control unit stores peak activity for each sensor to assist in evaluating specific locations. The host control unit determines the alarm set point for each TrueAlarm sensor, selectable as more or less sensitive as the individual application requires.

Timed/multi-stage selection

You can program the sensor alarm set points for timed automatic sensitivity selection, such as more sensitive at night, less sensitive during day. You can program the control unit to provide multi-stage operation for each sensor.

Sensor alarm and trouble LED indication

Each sensor base's LED pulses to indicate communications with the unit. If the control unit determines a sensor is in alarm, is dirty, or has some other type of trouble, the details are annunciated at the control unit and the sensor's base LED will turn on steadily. During a system alarm, the control unit will control the LEDs such that an LED indicating a trouble will return to pulsing to help identify the alarmed sensors.

TrueAlarm sensors
  • Sealed against rear air flow entry
  • Interchangeable mounting
  • EMI/RFI shielded electronics
Smoke sensors
  • Photoelectric technology sensing
  • 360° smoke entry for optimum response
  • Built-in insect screens
4098-9733 and 4098-9734 heat sensors

TrueAlarm heat sensors are self-restoring and provide rate- compensated, fixed temperature sensing, you can select with or without rate-of-rise temperature sensing. Due to its small thermal mass, the sensor accurately and quickly measures the local temperature for analysis at the fire alarm control unit.

You can select rate-of-rise temperature detection at the control unit for either 15°F or 20°F, (8.3°C or 11.1°C) for each minute. Fixed temperature sensing is independent of rate-of-rise sensing and you can program it to operate at 135°F or 155°F (57.2°C or 68°C). The 4098-9734 sensor provides an additional 190°F (88°C) set point.

In a slowly developing fire, the temperature may not increase rapidly enough to operate the rate-of-rise feature. However, an alarm will be initiated when the temperature reaches its rated fixed temperature setting.

You can program TrueAlarm heat sensors as a utility device to monitor for temperature extremes in the range of 32°F to 155°F (0°C to 68°C). This feature can provide freeze warnings, or alert you to HVAC system problems. Refer to panel specifications for availability.

Specifications
Communications and sensor supervisory powerIDNet or MAPNET II communications, auto-selected, one address for each base
Communications connectionsScrew terminals for in/out wiring, 18 to 14 AWG, 0.82 mm to 2.08 mm
Remote LED alarm indicator current1 mA typical, no impact to alarm current
Remote LED alarm indicator and relay connectionsColor coded wire leads, 18 AWG, 0.82 mm
UL listed operating temperature range32°F to 100°F, 0°C to 38°C
Operating temperature range32°F to 122°F, 0°C to 50°C
Storage temperature range0°F to 140°F, -18°C to 60°C
Humidity rangeHumidity range
4098-9714 smoke sensor air velocity rating0 to 4000 ft/min, 0 to 1220 m/min
Housing colorFrost white or black
Export Info
Made inMexico
Harmonized Tariff Code (HTC)85311001

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer/Electronic Payment and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> INTELLIGENT :    23 Items found.
FSV-951R
(3229)

NOTIFIER  FSV-951R

Notifier FSV-951R Series Very Intelligent Plug-in Early Warning (VIEW) Laser Smoke Detector. 0.03% to 1.00% (CLIP) or 0.02% to 2.00% (other) sensivity. With FlashScan and CLIP protocol systems. Advanced laser light source and 360° viewing angle. Optional relay, isolator and sounder bases. UL and MEA listed. FM, CSFM, BSMI and CCCF Approved. (replaces FSL-751)

4098-9756
(7075)

SIMPLEX TYCO  4098-9756

Simplex Tyco 4098-9756 Addressable Duct Sensor Housing with TrueAlarm Photoelectric Smoke Sensor. Includes relay, supervised output for multiple remote relays and 2 diagnostic LEDs. IDNet and MAPNET II communications. UL listed (requires separate 24 VDC fire alarm power).



 
FS-OSI-RI
(6933)

NOTIFIER  FS-OSI-RI

Notifier FS-OSI-RI Intelligent Addressable Single-ended Reflective Imaging Beam Smoke Detector suited for large open areas with high ceilings. 24 VDC. 12° field of view. Status LED indicators. UL and FM approved.



 
Page: 1 | 2 | All
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.