Detcon DM-700-CLO2 Electrochemical Smart Chlorine Dioxide (CLO2) 0-50 ppm Sensor Assembly with LED display. 4-20mA and Modbus RS-485 outputs. 316 Stainless Steel Housing. Water Proof, Corrosion Proof, Vibration Proof and Explosion proof. NEMA 4X. IP66. Class I, Div. 1, Groups B, C, & D. CSA and ATEX approvals.

967-747690-050   
Please Email us your request for quote   

Junction Box
Options
Integration Modules
Class 1; Div 1; Groups B, C, D – Zone I Group IIB+H2
Mounting Options
Additional Modules

   3 Weeks  ]
12 Variants of base SKU

Detcon Model 700 Series Sensors are a non-intrusive “Smart” sensors designed to detect and monitor oxygen and Toxic Gases in air using electrochemical sensor technology. The intelligent plug-in, field replaceable cell provides automatic recognition of gas type and range, and features over-sized gold-plated connections that help prevent corrosion. The Model 700’s rugged framework includes an intrinsically safe electro-polished 316 stainless steel housing with fully encapsulated electronics and dual layer surge protection. This innovative design virtually eliminates sensor failure due to water ingress, corrosion, vibration, and transient spikes. A primary feature of the Model 700 is embedded intuitive software that simplifies operator interface by guiding the user through routine calibration, configuration, and fault diagnostic functions using a built-in alpha/numeric display. The Model 700 is equipped with standard analog 4-20mA, and ModbusTM RS-485 outputs. Among its unique features is a wireless option that can be used with Detcon’s SmartWireless® product line. Additional integration options include a Remote Alarm Module (RAM), HART, and Foundation Fieldbus. Detcon’s toxic gas and oxygen sensors have a long shelf life and are supported by an industry-leading warranty.

Features Failsafe User-Friendly Interface
  • LED Display (With Antiglare Cover)
  • Full Text Display Method
  • Non-intrusive Interface
  • Auto Zero/Auto Span
  • Pre-emptive Fault Diagnostics
Environmentally Bulletproof
  • Electropolished 316SS Construction
  • 100% Epoxy Encapsulated Circuitry
  • Bulletproof I/O Protection
  • Water-Proof, Corrosion-Proof, Vibration-Proof
Modular and Serviceable
  • Modular Design
  • Plug and Play Components
  • Quick Thread Release (For Sensor Replacement)
  • Integral Calibration Port
Applications
  • Oil & Gas
  • Chemical Plants
  • Food and Beverage
  • Steel Mills
  • Pulp and Paper
  • Refineries
  • Wastewater Treatment Plants
  • Utilities

System Specifications
Sensor TypeContinuous diffusion/adsorption
3-electrode electrochemical cell
Plug-in field replaceable Type
Measurement Range0-50 ppm
Accuracy/Repeatability±2% FS
Response/Clearing TimeT90≤120 seconds
OutputsLinear 4-20 mA DC
RS-485 MODBUS-RTU
Electrical ClassificationExplosion proof
CSA and US (NRTL)
Class I, Division 1, Groups B, C, D (Tamb = -40°C to +50°C)
Class I, Zone 1, Group IIC
ATEX
II 2 G Ex d ib IIB + H2 T4 GB
Ingress ProtectionNEMA 4X, IP66
Safety ApprovalsCCSAUS
ATEX
CE Marking
SIL2 Certified to IEC 61508
Environmental Specifications
Operating Temperature Range-4 to 104oF/-20 to 40oC
Storage Temperature Range-31 to 131oF/-35 to 55oC
Operating Humidity Range10-95% RH non-condensing
Mechanical Specifications
Dimensions7"H x 2.2" Dia.; 178mmH x 65mm Dia. (sensor assembly only)
11"H x 6.1"W x 3.75"D; 280mmH x 155mmW x 96mmD (with junction box)
Mechanical Connection:
Mounting holes (J-box) 5.5"; 140mm center to center
Weight2 lbs; 0.907kg (sensor only)
6 lbs; 2.72kg (w/aluminum j-box)
9 lbs; 4.08kg (w/stainless steel j-box)
Electrical Specifications
Power Input11-30 VDC
Power ConsumptionNormal operation = 30mA @24V (<0.75 watt)
Maximum = 50mA @24V (1.2 watts)
Inrush Current500mA @ 24V (typical)
RFI/EMI ProtectionComplies with EN50270
Analog OutputLinear 4-20mA DC (1,000 ohms max loop load @ 24VDC)
0mA: All Fault Diagnostics
2mA: In-Calibration
4-20mA: 0-100% full-scale
22mA: Over-range condition
Serial RS-485 OutputRS-485 ModbusTM RTU
Baud Rate (optional)9600 BPS (9600,N,8,1 Half Duplex)
Status Indicators4-digit LED display with gas concentration
Full-script menu prompts for AutoSpan
Set-up Options, and Fault Reporting
Faults MonitoredLoop, Input Voltage, Missing Sensor, Zero, Processor, Memory, Calibration
Cable RequirementsPower/Analog
3-wire shielded cable
Maximum distance is 13,300 feet with 14 AWG
Serial Output
2-wire twisted-pair with ground, shielded communication cable specifically for use with RS-485 installations
Maximum distance is 4,000 feet to last sensor
I/O ProtectionOver-voltage, Miswiring, EMI/RFI Immunity
Export Info
Made inUnited States
Harmonized Tariff Code (HTC)9027102000

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> ACCESSORIES - RELATED - CONSUMABLES :    3 Items found.
943-000000-000
(6566)

DETCON  943-000000-000

Detcon Calibration Sleeve/Wind Guard for use with sensor splash guard for all Detcon sensor heads.



 
377-747601-050
(6175)

DETCON  377-747601-050

Detcon Chlorine Dioxide (CLO2) plug-in sensor for DM-700-CLO2 (0-50ppm)



 
S927-555500-100
(6607)

DETCON  S927-555500-100

Detcon DM-700-EC Electrochemical Universal ITM (Intelligent Transmitter Module) Spare Part for SO2, C2H2, AsH3, Br2, C4H6, CO, CL2, CLO2, B2H6, C2H5OH, C2H5SH, C2H4, C2H4O, F2, CH2O, H2, HBr,m HCL, HCN, HF, CH3OH, CH3SH, NO, NO2, O3, PH3 or SiH4

> CHLORINE DIOXIDE :    6 Items found.
M001-0072-000
(5996)

MPOWER  M001-0072-000

mPower UNI MP100 Portable Single Gas Detector for detection of Chlorine Dioxide (ClO2) 0-1ppm. Includes large LCD display, 6 Bright Red Flashing LED, Vibrating and 90dB Audible Alarm Port. IP67, Event Logger, ATEX and UL approval for Class I Div 1.



$398.40 
BWS1-V-Y
(6385)

BW  BWS1-V-Y

BW Solo Serviceable Single-gas Detector for Chlorine Dioxide (ClO2) 0-1 ppm. Small and lightweight. One button operation, 3.6V 1.65Ah Lithium Battery. Visual, vibrating and audible alarms. Optional wireless version. IP66/68. ATEX, IECEx and CSA approvals for Class I Div 1.

961-770026-001G
(6354)

DETCON  961-770026-001G

Detcon DM-100-CLO2 Electrochemical Chlorine Dioxide (ClO2) 0-1ppm or 0-50ppm Sensor Assembly with optional loop powered display. 4-20 mA. Features intelligent electronices, non-intrusive operator interface and comprehensive fault diagnostics. Optional 316 Stainless Steel Housing. 3/4" NPT thread. XP-instrinsically safe. Class I, Div. 1, Groups A, B, C, & D.

S3KUL2-XNXXSX1SS
(688)

HONEYWELL  S3KUL2-XNXXSX1SS

Honeywell Series 3000 MkII Gas Detector Transmitter, with aluminum housing (optional stainless steel) for monitoring CHLORINE DIOXIDE (ClO2) with electrochemical sensor, 2-wire 4-20mA loop, LCD Display, 0-1.00ppm Available Approvals UL Class I, Div 1 & 2, ATEX Zone 0 and IECEx.

Configure

$1,737.61 
XNXUTAENNNNN-XNXXSX1SS
(838)

HONEYWELL  XNXUTAENNNNN-XNXXSX1SS

Honeywell XNX Universal Gas Detector Transmitter for monitoring Chlorine Dioxide (ClO2) 0-1.00ppm compatible with all Honeywell gas sensing technologieswith aluminum housing. 3-wire 4-20mA HART loop, backlit LCD Display, option for Modbus, Foundation H1 Fieldbus, local Hart and relay outputs UL Certified Class 1, Div 1 Groups A, B, C, D / ATEX Zone 1, SIL-2

Configure

$2,221.73 
967-777790-001
(6076)

DETCON  967-777790-001

Detcon DM-701-CLO2 Electrochemical Smart Chlorine Dioxide (CLO2) 0-1 ppm Sensor Assembly with LED display. 4-20mA and Modbus RS-485 outputs. 316 Stainless Steel Housing. Water Proof, Corrosion Proof, Vibration Proof and Explosion proof. NEMA 4X. IP66. Class I, Div. 1, Groups B, C, & D. CSA and ATEX approvals.

Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.