Notifier FCM-1 Series Addressable Control Module for Notification Appliances (horns, strobes, speakers, etc). Two-wire SLC loop. High noise immunity. 15 to 32 VDC. UL, FM, CSFM, MEA and FDNY Approved.

Please Email us your request for quote   

   2 Days  ]

FCM-1(A) Control Module: The FCM-1(A) Addressable Con- trol Module provides Notifier intelligent fire alarm control pan- els a circuit for Notification Appliances (horns, strobes, speakers, etc.). Addressability allows the FCM-1(A) to be acti- vated, either manually or through panel programming, on a select (zone or area of coverage) basis.

FlashScan® (U.S. Patent 5,539,389) is a communication pro- tocol developed by NOTIFIER Engineering that greatly enhances the speed of communication between analog intelli- gent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new infor- mation, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs.

FEATURES

  • Built-in type identification automatically identifies these devices to the control panel.
  • Internal circuitry and relay powered directly by two-wire SLC loop. The FCM-1(A) module requires power (for horns, strobes, etc.), or audio (for speakers).
  • Integral LED “blinks” green each time a communication is received from the control panel and turns on in steady red when activated.
  • LED blink may be deselected globally (affects all devices).
  • High noise immunity (EMF/RFI).
  • The FCM-1(A) may be used to switch 24-volt NAC power, audio (up to 70.7 Vrms).
  • Wide viewing angle of LED.
  • SEMS screws with clamping plates for wiring ease.
  • Direct-dial entry of address 01– 159 for FlashScan loops, 01 – 99 for CLIP mode loops.
  • Speaker, and audible/visual applications may be wired for Class B or A (Style Y or Z).
Applications

The FCM-1(A) is used to switch 24 VDC audible/visual power, high-level audio (speakers).

NOTE: Refer to the SLC Manual (PN 51253) for details regarding releasing applications with the FCM-1(A). Refer to the FCM-1-REL datasheet (DN-60390) for new FlashScan® releasing applications.

Construction

The FCM-1(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit.

Operation

FCM-1(A) uses one of 159 possible module addresses on a SLC loop (99 on CLIP loops). It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notifica- tion Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. The FCM-1(A) supervises Class B (Style Y) or Class A (Style Z) notification or control circuits.

Upon code command from the panel, the FCM-1(A) will dis- connect the supervision and connect the external power sup- ply in the proper polarity across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned ON. The external power supply is always relay isolated from the com- munication loop so that a trouble condition on the external power supply will never interfere with the rest of the system.

Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the con- trol panel, so as to differentiate between a module and a sen- sor address.

Agency Listings and Approvals

In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status.

  • UL: S635
  • ULC: S3705 (A version only)
  • FM Approved
  • CSFM: 7300-0028:0219
  • MEA: 14-00-E
  • FDNY: COA #6067, #6065

FCM-1(A) SPECIFICATIONS
Normal operating voltage: 15 to 32 VDC
Maximum current draw: 6.5 mA (LED on).
Average operating current: 350 μA direct poll, 375 μA group poll with LED flashing, 485 μA Max. (LED flashing, NAC shorted.)
Maximum NAC Line Loss: 4 VDC.
External supply voltage (between Terminals T10 and T11): Maximum (NAC): Regulated 24 VDC; Maximum (Speakers): 70.7 V RMS, 50W.
Drain on external supply: 1.7 mA maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply.
Max NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rat- ing is 2A.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box.
Accessories: SMB500 Electrical Box; CB500 Barrier
Export Info
Made inMexico

 Info/Quote Request
 Reseller & Volume Discounts
 Shipping Rates

B2B Checkout Options: Designated Carrier and Tax-Exempt purchase
Payment Options: Credit Card, Credit Card Over the Phone, PAYPAL, Wire Transfer/Electronic Payment and Check

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> NOTIFIER :    42 Items found.
HS-NCM-MF__
(4326)

NOTIFIER  HS-NCM-MF

Notifier HS-NCM High-Speed Network Communications Module. Single or Multi-mode versions available. Allow connection from Notifier Panels to NOTI•FIRE•NET with a fiber-optic cable or twisted-pair wire. NFPA Style 4 (Class B) or Style 7 (Class A) operation. 24 VDC, 100Mb baud transmission rate. UL, ULC, CSFM and FM approved.

CPU2-3030D
(6931)

NOTIFIER  CPU2-3030D

Notifier CPU2-3030D Central processing unit for an NFS2-3030 system. Keypad/display installed; includes 640-character backlit LCD display, QWERTY programming and control keypad. Requires an AMPS-24(E) power supply.

Page: 1 | 2 | 3 | All
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.