Industrial CO2 Detector Specifications |
Measurement Range | 0 - 50,000ppm (5%) display |
Display Resolution | 10ppm at 0~10,000ppm; 100ppm at 10,001~50,000ppm |
Accuracy | +/-200ppm or +/-10% reading |
Pressure Dependence | Auto pressure compensation, built in barometer. (50 to 110 kPa) |
Response Time | <2min by 90% |
AL1 | 5,000ppm Default (5,000ppm or 5,000 TWA) |
AL2 | 1.5% Default (5,000, 1.0%, 1.5%, 2.0%, 2.5%, 3.0%) |
AL3 | 3.0% Default (2.0%, 2.5%, 3.0%,3 .5%, 4.0%) |
Sound Alarm | 80db@10cm |
Warm-Up Time | <60 seconds at 22°C |
Monitor Specifications |
Power Input | 9~32VDC (12~24VDC recommended), 2A. |
Backup Battery | 6VDC (5.4V~7.0V), recommended capacity is 12AH |
Relay 1 | Dry contact relay controlled by AL1 (2Amp) (NO or NC) |
Relay 2 | Dry contact relay controlled by AL2 (2Amp) (NO or NC) |
Relay 3 | Dry contact relay (Triggered by power loss to monitor) |
4-20mA CO 2 | Range 0-50,000ppm |
4-20mA Temperature | Range 32 to 122° F (0-50°C) |
Dimensions | 8.25-inch x 7.8-inch x 3-inch |
Weight | 1.5lbs (Monitor only) |
Ingress Protection | IP64 |
Temperature Specifications |
Temperature Range | 32°F to 122°F (0°C to 50°C) |
Display Resolution | 0.1°F (0.1°C) |
Accuracy | ±1.5°C(±2.7°F) when CO 2 level is below first alarm level |
Response Time | 20-30 minutes (case must equalize with environment) |
Operating Conditions |
Temperature | 32°F to 122°F (0°C to 50°C) |
Humidity Range | 0 ~ 95% RH non-condensing |