Model 4098-9757 QuickConnect2 sensor design
provides:
- TrueAlarm photoelectric analog sensing and IDNet two-wire addressable communications combined into one assembly
- Quick and easy connection to a 4098-9788 base (required, ordered separately)
- Operation for ceiling or wall mounting
- Operation for use with Simplex ® models 4007ES, 4010, 4010ES, 4100ES with IDNet 2 and IDNet 2+2 Modules, and 4100ES/4100U Fire Alarm Control Panels with IDNet Module 4100-3106
- UL listed to Standard 268
QuickConnect2 sensors communicate to the
control panel to provide the following TrueAlert
analog sensing operation features:
- Smoke sensitivity that is accurately maintained at the selected level (determined by the control panel)
- 4007ES, 4010ES, and compatible 4100ES/4100U Series control panels provide seven levels of sensitivity from 0.2% to 3.7%/ft of obscuration (refer to page 2 for application details)
- 4010 Series control panels provide three levels of sensitivity of 2.5, 3.0, or 3.7%/ft obscuration
- Sensitivity monitoring that satisfies NFPA 72 sensitivity testing requirements
- Automatic environmental compensation
- Automatic, once per minute individual sensor calibration check verifies sensor integrity
- Ability to display and print detailed sensor information in plain English language
- Tracking of excessive dirt accumulation
4098-9788 base provides stationary wiring
terminals and quick snap-in sensor connections:
- Mounting is on a 4” square, 4” octagonal, or single gang box (supplied separately)
- 4098-9832 Adapter Plate is available for retrofit and certain mounting methods (refer to page 2)
Functional and architecturally styled chamber
enclosure details:
- Louvered design enhances smoke capture by directing flow to chamber
- Entrance areas are minimally visible when ceiling mounted
- Chamber is easily accessible for cleaning
- Designed for EMI compatibility
- Internal magnetic test feature that activates alarm
Integral red LED (with red lens) indicates:
- Power-on when pulsing, Alarm or Trouble when steady on (a remote LED is not supported)
- Refer to data sheet S4098-0019 for sensor bases that support remote LED connections and additional TrueAlarm analog detection features
For applications that only require basic TrueAlarm
features, the 4098-9757 QuickConnect2 sensor provides
addressable analog sensing in a cost-effective compact
package. The control panel monitors and maintains the
selected sensitivity of the 4098-9757 as well as providing
automatic compensation for environmental conditions
such as dust, dirt, and component degradation, and
TrueAlarm data capture for each sensor.
QuickConnect2 Mounting. Wiring connections are
made to a 4098-9788 base which provides a secure and
quick connection for the 4098-9757 sensor. Sensor and
communications electronics are contained in the
4098-9757 sensor assembly.
Sensor Alarm and Trouble LED Indication. The
control panel also determines when individual sensors
need cleaning. Dirty sensors, or other sensor troubles, will
automatically be annunciated at the control panel and that
sensor’s LED will light steadily. In an alarm condition,
the alarmed sensor’s LED will light steadily. (LED
operation is controlled by the panel. During system alarm,
a sensor LED that was lit to indicate trouble will return to
pulsing to conserve communications power as long as it is
not in alarm.)
Sensor Locations
Sensor locations should be determined only after careful
consideration of the physical layout and contents of the
area to be protected. Refer to NFPA 72, the National Fire
Alarm and Signaling Code. On smooth ceilings, spacing
of 30 ft (9.1 m) may be used as a guide.
For detailed installation information, refer to 574-709,
4098 Detectors, Sensors, and Bases Application Manual.
For mounting base 4098-9788 installation instructions,
defer to 574-706, 4098 Smoke/Heat Base Installation
Instructions.